4.12 False
Echo Edit
Page 36
In some cases, the above graph will appear, and the valid echoe
is above the envelope.
If MultiWave Option=disable, the system considers the above to
be One valid echo, and the intensity is the highest point of the
wave .
If MultiWave Option=Enalbe, the system separates the above
wave and considers that there are two valid echoes.
System separates the above wave and considers that there are
two valid echoes
When the existing false echo curve still does not meet the
requirements, the false echo curve can be edited.
When the LCD displays 4.12, press
setting menu. Display in LCD is as follows.
Four values need to be input for each edit,
the starting point distance/the starting point Amplitude;
the ending point distance/the ending point Amplitude.
According to the input value, the system adds a straight line
connecting two points to the existing false echo.
Example:
SLN 700 SmartLine NCR Level Transmitter User's Manual
to enter the Multi Wave
Revision 2