Propane Burner Application - Riello G120 Installation, Use And Maintenance Instructions

Forced draught natural gas/propane burner
Table of Contents

Advertisement

PROPANE BURNER APPLICATION

The burner leaves the factory to run on
natural gas. It is available a kit, on request,
that allows the burner to run on propane.
TECHNICAL FEATURES
The thermal output and operating range of
burners converted to use propane are the
same as for burners running on natural gas.
GAS Family 3:
Net calorific value: 24 - 34 kWh/m
3
21,000 ÷ 29,300 kcal/m
Min. pressure 25 - max. 50 mbar.
LIST OF KIT'S COMPONENTS
Quantity
Component
1
Reducer
1
Diffuser 1,3
1
Adhesive label
1
Instructions
6
Diaphragm
CONVERSION
On the combustion head of the burners, diaphragm (4) should
be replaced, and natural gas nozzle (1) replaced with the one
used for propane, and a reducer (3) should be added.
Proceed as follows, (fig. A):
Disassemble the ignition electrode and the ionisation probe.
Replace diaphragm (4) and replace natural gas nozzle (1) (marked 1.7) with the one supplied used for propane
(marked 1.3).
Remove the distributor - diffuser disc once the screws have been removed.
Insert reducer (3), refit the distributor-diffuser disc and then tighten the fastening screws.
Reassemble the electrode and the ionisation probe in the position foreseen in the instructions for the natural gas.
Affix the adhesive label as illustrated in fig. B.
2903332
1
3
2
16
GB
3
4
Fig. A
D7345
Fig. B
Adhesive data plate
supplied as equipment
D4005

Advertisement