Fujitsu Comfort Series Service Manual page 34

Hide thumbs Also See for Comfort Series:
Table of Contents

Advertisement

Troubleshooting 13
OUTDOOR UNIT Error Method:
Heatsink Thermistor Error
Detective Actuators:
Heatsink temperature thermistor
Forecast of Cause :
1. Connector connection failure, open
2. Thermistor failure
3. Inverter PCB failure
Check Point 1 : Check the connector connection and cable open
Connector connection state check
Cable open check
OK
Check Point 2 : Check the thermistor
Thermistor characteristics check
(Disconnect the thermistor from the PCB and check.)
* For the thermistor characteristics, refer to the "Service Parts Information 5".
OK
Check Point 3 : Check voltage of Inverter PCB (DC5.0V)
Main PCB P700:1-3 voltage value =5V
Remove the thermistor from Inverter PCB, check the voltage.
1
2
3
1
2
3
P700
If the voltage does not appear, replace Inverter PCB,
and execute the check operation again.
Indicate or Display:
Hydraulic unit :
Green Red
7
7
n : n times blinking
Detective details:
Heatsink temperature thermistor short or open detected
03-15
Outdoor unit :
Mode Error L1 L2
2
7
7
: Light OFF
: Light ON
DC
L3
L4
L5
L6
n : n times blinking

Advertisement

Table of Contents
loading

This manual is also suitable for:

Comfort woya100kltComfort wsya100ml3

Table of Contents