Load A Configuration For All Parameters From A File (Init > Load); Display Firmware Revision Number (Init > Ver.n); Update Firmware Revision (Init > Ver.u); Reset To Factory Default Parameters (Init > F.dft) - Omega CN16Pt User Manual

Temperature & process controllers
Hide thumbs Also See for CN16Pt:
Table of Contents

Advertisement

PLATINUM
Series User's Guide
TM
Confirm the SAVE command. This saves the configuration to the file number specified. If the
SAVE operation fails, the failure code w004 is displayed. If the SAVE operation is successful,
doNE is displayed.
4.8
Load a Configuration for All Parameters from a File (INIt > LoAd)
Select the Load a Configuration (LoAd) command. If no thumb drive is present the failure code
E010 is displayed. Otherwise, a numeric designation for the file to be loaded is then specified
and confirmed before the LoAd command executes.
Select a numeric file name from the range 0–99.
Confirm the LoAd command. This loads the configuration from the file number specified. If
the LoAd operation fails, the failure code w003 is displayed. If the LoAd operation is
successful, doNE is displayed.
4.9
Display Firmware Revision Number (INIt > VER.N)
Select the Display Firmware Revision Number (VER.N) function. The currently installed version
number is displayed in the format 1.23.4 where "1" is the major revision number, "23" is the
minor revision number, and "4" is the bug fix update number.
4.10 Update Firmware Revision (INIt > VER.U)
Select the Update Firmware Revision (VER.U) function. Note that updating your firmware will
reset the unit to factory defaults as well. If you want to keep you configuration settings, save
them before installing new firmware.
The LED display shows ok? and requires confirmation. Confirm the firmware update. New
firmware will then be read from a thumb drive connected to the USB port.
4.11 Reset to Factory Default Parameters (INIt > F.dFt)
Select the Reset to Factory Default Parameters (F.dFt) function. The LED display shows ok?
and requires confirmation.
Confirm the parameter reset.
4.12 Password-Protect Initialization Mode Access (INIt > I.Pwd)
Select the Password Protect Initialization Mode Access (I.Pwd) function.
Navigate to the desired setting. Settings include the following:
No – Do not require a password for INIt Mode (factory default)
yES – Require a password for INIt Mode; users will be prompted for this password
when selecting INIt
Select the indicated setting.
If yES, set the numeric password from the range 0000–9999.
Confirm the password.
4.13 Password-Protect Programming Mode Access (INIt > P.Pwd)
Select the Password Protect Programming Mode Access (P.Pwd) function.
Reference Section: Initialization Mode (INIt)