F US Clamp-on Communications Module Installation
Figure 3-4
8. Gently press the Communications Module down to connect it to the I/O Module.
9. Tighten the captive screws to secure the Communications Module and the I/O Module.
10.If using Ethernet IP, connect the Ethernet connector.
Note
Ethernet Web Utility Discovery.zip
This Web utility is used to locate communications modules on the same network.
The web utility can be found at
http://www.fieldserver.com/techsupport/utility/downloads.php. (Discovery.zip)
The default IP address is: 192.168.0.2
11.If using RS485, connect RS-485 connector to J1.
12.After Communications Module installation is complete, replace the Communications
Module cover and tighten the captive screw.
13.Close the flow meter cover and secure the side latch.
14
①
Ethernet Connector J5
②
SW1
③
SW2
④
J3
SITRANS F US Clamp-on Communications Module A5E31949269
⑤
RS-485 Connector J1
⑥
Captive Screw and Standoff
⑦
Standoff
SITRANS F US Clamp-on Communications Module
Compact Hardware Installation Instructions, 2/2014, A5E32586525-AD