Mitsubishi Electric FR-E8TR Instruction Manual page 39

Rs-485 2 port terminal block
Table of Contents

Advertisement

Pr.
550
NET mode operation command source
D012
selection
551
PU mode operation command source
D013
selection
726
Auto Baudrate/Max Master
N050
727
Max Info Frames
N051
Initial
Name
value
9999
9999
255
1
OPERATION VIA COMMUNICATION FROM RS-485 TERMINALS
Setting range
The communication option is the command
0
source in the NET operation mode.
The RS-485 terminals are the command source
2
in the NET operation mode.
Communication option is recognized
automatically.
Normally, the RS-485 terminals are the
9999
command source. When the communication
option is installed, the communication option is
the command source.
The RS-485 terminals are the command source
2
in the PU operation mode.
The USB connector is the command source in
3
the PU operation mode.
The operation panel is the command source in
4
the PU operation mode.
The USB is recognized automatically.
Normally, the operation panel is the command
9999
source. When the USB is connected, the USB
connector is the command source.
Auto baud rate (bit 7)
0: inactive, 1: active
0 to 255
Max Master (bit 0 to bit 6) setting range: 0 to 127
Maximum address for master node
Set the maximum number of frames that the
1 to 255
inverter can transmit while it owns the token.
Description