 Common terminal
Terminal
Common
symbol
RS-485 communication
SG
common, analog common
Contact input common (sink
(negative common))
External transistor common
SD
(source (positive common))
24 VDC power supply common
External transistor common (sink
(negative common))
PC
Contact input common (source
(positive common))
SD
24 VDC power supply
SE
Open collector output common
18
PRE-OPERATION INSTRUCTIONS
Terminal name
Common terminal for RS-485 communication and
frequency setting signals (terminal 2 or 4). Do not earth
(ground).
Common terminal for the contact input terminal (sink logic)
and terminal FM.
Connect this terminal to the power supply common
terminal of a transistor output (open collector output)
device, such as a programmable controller, in the source
logic to avoid malfunction by undesirable current.
Common output terminal for 24 VDC 0.1 A power supply
(terminal PC). Isolated from terminals SG and SE.
Connect this terminal to the power supply common
terminal of a transistor output (open collector output)
device, such as a programmable controller, in the sink logic
to avoid malfunction by undesirable current.
Common terminal for contact input terminal (source logic).
This terminal can be used as 24 VDC 0.1 A power supply.
Common terminal for terminals RUN and FU.
Terminal function description
Rated
specification
Power supply
voltage range:
22 to 26.5 VDC
Permissible load
current: 100 mA