Daikin FXTQ12PVJU Installation Manual

Vrv system inverter air conditioners
Hide thumbs Also See for FXTQ12PVJU:

Advertisement

SYSTEM Inverter Air Conditioners
MODELS
Air Handling Unit
FXTQ12PVJU
FXTQ18PVJU
FXTQ24PVJU
FXTQ30PVJU
FXTQ36PVJU
FXTQ42PVJU
FXTQ48PVJU
FXTQ54PVJU
Read these instructions carefully before installation.
Keep this manual in a handy place for future reference.
This manual should be left with the equipment owner.
Lea cuidadosamente estas instrucciones antes de instalar.
Guarde este manual en un lugar a mano para leer en caso de tener alguna duda.
Este manual debe permanecer con el propietario del equipo.
INSTALLATION MANUAL
English
Español

Advertisement

Table of Contents
loading

Summary of Contents for Daikin FXTQ12PVJU

  • Page 1 INSTALLATION MANUAL SYSTEM Inverter Air Conditioners MODELS Air Handling Unit FXTQ12PVJU FXTQ18PVJU English FXTQ24PVJU FXTQ30PVJU FXTQ36PVJU Español FXTQ42PVJU FXTQ48PVJU FXTQ54PVJU Read these instructions carefully before installation. Keep this manual in a handy place for future reference. This manual should be left with the equipment owner.
  • Page 2: Table Of Contents

    VRV SYSTEM Inverter Air Conditioners Installation manual CONTENTS • If refrigerant gas leaks during installation, ventilate the area immediately. Refrigerant gas may produce toxic 1. SAFETY CONSIDERATIONS ........... 1 gas if it comes in contact with fi re. Exposure to this gas 2.
  • Page 3 Do not install the air conditioner in the following loca- device is shorted and operated forcibly, or parts other tions: than those specifi ed by Daikin are used, fi re or explo- Where a mineral oil mist or oil spray or vapor is sion may occur.
  • Page 4: Before Installation

    BEFORE INSTALLATION FOR THE FOLLOWING ITEMS, TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED. WARNING a. Items to be checked after completion of work • Entrust installation to the place of purchase or a qualifi ed serviceman. Improper installation could lead to leaks and, in If not properly done, what is Items to be checked Check...
  • Page 5: Preparations Before Installation And Installation

    • Where the ceiling is strong enough to bear the indoor WARNING unit weight. • If the supporting structural members are not strong enough • Where the false ceiling is not noticeably on an incline. to take the unit’s weight, the unit could fall out of place and •...
  • Page 6: Refrigerant Piping Work

    REFRIGERANT PIPING WORK Field piping fitting port (brazed) 〈Observe the requirements listed below for refrigerant Field piping piping sizes.〉 Liquid 12 · 18 type 2/8 in. 4/8 in. 24 · 30 · 36 · 3/8 in. 5/8 in. 42 · 48 · 54 type 〈Execute heat insulation work completely on both sides of the gas piping and the liquid piping.
  • Page 7: Drain Piping Work

    • Do not connect the drain piping directly to sewage pipes that NOTE smell of ammonia. The ammonia in the sewage might enter • Do not use fl ux when brazing refrigerant piping. Therefore, the indoor unit through the drain piping and corrode the heat use the phosphor copper brazing fi...
  • Page 8: Wiring Example

    WIRING EXAMPLE DANGER • Do not ground units to water pipes, telephone wires or HOW TO CONNECT WIRINGS lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death, and Remove the front panel (upper). to gas pipes because a gas leak could result in an explosion Top panel Low-voltage hole...
  • Page 9 [ PRECAUTIONS ] Terminal block (3P) Terminal block (6P) • Refer to the “REMOTE CONTROLLER INSTALLATION MANUAL” on how to install and lay the wiring for the remote controller. • See also the “Wiring Diagram Label” located inside the unit’s fan housing.
  • Page 10 No. 3 system When including BS unit CONTROL BY 2 REMOTE CONTROLLERS (Con- trolling 1 indoor unit by 2 remote controllers) Power supply single phase Outdoor unit BS unit • When using 2 remote controllers, one must be set to “MAIN” 60Hz 208-230V and the other to “SUB”.
  • Page 11: Field Setting And Test Run

    [ PRECAUTIONS ] SECOND CODE NO. • Crossover wiring is needed when using group control and 2 remote controllers at the same time. Mode No. • Connect the indoor unit at the end of the crossover wire (P ¹ , FIRST P ²...
  • Page 12 • The settings can be changed to not display. • When installing the unit in a place with much dusts, set the fi lter sign display time to shorter intervals (1,250 hours). • Explain it to the customer that the fi lter needs to be cleaned regularly to prevent clogging and also the time that is set.