Unit installation

7.1.3 Installation site requirements of the indoor unit

Installer reference guide
70
INFORMATION
Also read the precautions and requirements in the
precautions" [
4
The indoor unit is designed for indoor installation only and for the following
ambient temperatures:
-
Space heating operation: 5~30°C
-
Space cooling operation: 5~35°C
-
Domestic hot water production: 5~35°C. If EKECBUAF6V is installed, ambient
temperature is limited to 5~32°C.
INFORMATION
Cooling is only applicable in case of reversible models.
Mind the following measurements guidelines:
Maximum refrigerant piping length between indoor unit and
outdoor unit
Minimum refrigerant piping length between indoor unit and
outdoor unit
Maximum height difference between indoor unit and outdoor
unit
Mind the following spacing installation guidelines:
CAUTION
Install the indoor unit at a minimum distance of 1 m from other heat sources (>80°C)
(e.g. electrical heater, oil heater, chimney) and combustible materials. Otherwise the
unit may be damaged or in extreme cases catch fire.
[
mm
≥100
≥500
INFORMATION
Serviceability may be impacted, if the indicated clearances cannot be maintained.
INFORMATION
If you have limited installation space, do the following before installing the unit in its
final position:
 10].
]
a
a ≥100
a+b ≥600
b ≥300
"7.4.4 To connect the drain hose to the
"2  General safety
b
4
drain" [
 86].
ERGA04~08EAV3+V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1 – 2022.01
30 m
3 m
20 m