Additional Installation Site Requirements Of The Outdoor Unit In Cold Climates - Daikin ERGA06EAV3H Installer's Reference Manual

Hide thumbs Also See for ERGA06EAV3H:
Table of Contents

Advertisement

7.1.2 Additional installation site requirements of the outdoor unit in cold climates

ERGA04~08EAV3+V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1 – 2022.01
In areas with low ambient temperatures and high humidity, or in areas with heavy
snowfall, remove the suction grille to ensure proper operation.
Non-exhaustive list of areas: Austria, Czech Republic, Denmark, Estonia, Finland,
Germany, Hungary, Latvia, Lithuania, Norway, Poland, Romania, Serbia, Slovakia,
Sweden, ...
1 Remove the screws holding the suction grille.
2 Remove the suction grille, and dispose of it.
3 Reattach the screws to the unit.
1
3
a Suction grille
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
c
a Snow cover or shed
b Pedestal
c Prevailing wind direction
d Air outlet
e EKFT008D option kit
In any case, provide at least 300  mm of free space below the unit. Additionally,
make sure the unit is positioned at least 100  mm above the maximum expected
level of snow. See
"7.3 Mounting the outdoor
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.
2
a
c
b
e
4
unit" [
7
Unit installation
|
a
 79] for more details.
Installer reference guide
69

Advertisement

Table of Contents
loading

Table of Contents