GENERAL INFORMATION
RECIRCULATION OPERATION
MANUALLY OPERATE PUMP
When set the "Recirc. Pump" ON, the recirculation
pump is ON for 5 minutes or until the return water tem-
perature reaches approximately 15 F below the setting
temperature.
1.6.5.3 HIGH ALTITUDE
ADJUSTMENT
1. Press the " SETTINGS " button.
SET POINT
BACK
ENTER
STATUS
SERVICE
MODE
2. Press the " ▼ " or " ▲ " button until Tankless Con-
fig " is displayed, and press ENTER " to confirm.
SETTINGS
None
BACK
ENTER
STATUS
SERVICE
MODE
3. Press the " ▼ " or " ▲ " button until "Elevation" is
displayed, and press the " ENTER " button.
BACK
SETTINGS
Recirc.Pump Modes
BACK
ENTER
SETTINGS
STATUS
SERVICE
MODE
Tankless Config
SET POINT
BACK
SETTINGS
BACK
ENTER
SETTINGS
STATUS
SERVICE
MODE
Tankless Config
BACK
ENTER
STATUS
SERVICE
MODE
BACK
SETTINGS
STATUS
Elevation
BACK
ENTER
SETTINGS
STATUS
SERVICE
MODE
OFF
ENTER
STATUS
SERVICE
MODE
27
4. The factory setting is " Sea Level Press the "▼"
ENTER
STATUS
SERVICE
MODE
1.6.5.4 WATER SAVING CONTROL
1. Press the " SETTINGS " button.
Recirc.Pump Modes
BACK
SETTINGS
OFF
ENTER
SERVICE
MODE
BACK
SETTINGS
Tankless Config
BACK
SETTINGS
STATUS
SERVICE
IKONIC Tankless Water Heater Service Manual
or "▲" button to select "Low Altitude", "Med. Al-
titude" and "High Altitude", and press "ENTER" to
confirm.
Sea Level
BACK
SETTINGS
STATUS
SECTION
Recirc.Pump Modes
Sea Level
BACK
SETTINGS
STATUS
Low Altitude
Med. Altitude
High Altitude
ENTER
STATUS
SERVICE
MODE
SET POINT
BACK
SETTINGS
STATUS
SET POINT
ENTER
STATUS
SERVICE
MODE
ENTER
MODE
ENTER
SERVICE
MODE
HIGH-ALTITUDE
0 – 2,000 ft
ENTER
SERVICE
MODE
(0 m – 610 m)
2,001 ft – 5,400 ft
(610 m – 1,650 m)
5401 ft – 7,900 ft
(1,650 m – 2,410 m)
7,901 ft – 10,200 ft
(2,410 m – 3,110 m)
ENTER
SERVICE
MODE