Issued: Oct 2017 Revision: AB Issued: Feb 2019 Rheem Solahart 874812XF 876812XF 874T16XF 876T16XF 874820XF 874820XF/J 876820XF 874T26XF 876T26XF 10143267 874826XF/J 10143268 First Issued: 10/2017 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
COMPONENT REPLACEMENT PROCEDURES ............. 52 DOCUMENT REVISION HISTORY ................... 60 TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
If the earth path of the appliance is intact, the problem is with the household wiring. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
20L – Propane gas 26L – Natural gas 26L – Propane gas TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 6
(offset) to compensate for temperature losses in the pipework, between the water heater outlet and sanitary fixtures. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 7
Wi-Fi network or a compatible mobile device are not available. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
WIRING DIAGRAM TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Note: The preset outlet temperature setting of the water heater must be set at 48°C prior to the commencement of this procedure. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
7. Once the post-purge operation ends (up to 6 minutes) power to the Fan Motor (25) is cut and the Fan (24) stops. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 11
X = Flame sensor is not detecting flame. O = Flame sensor is detecting flame TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
In-series gas boosting Solar Loline Installation TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
(refer to diagram below). TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
The water temperature can be decreased from any setting whether hot water is flowing or not. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 15
* Temperatures above 48 degrees are not available on 876 series as these units have a maximum selectable temperature of 48 C at all locations. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 16
TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 17
C when 50 C is displayed with 876 series models TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 18
Increases the general purpose temperature setting. (down button) Decreases the general purpose temperature setting. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Water flow control valve closed Bath Fill operation finished TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 20
MUST be connected to the same phase for EziSET to operate correctly. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
PCB. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 22
J0 - J9 U0 - U9 Operational Flow Chart Section TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Note: see page 22 for details on interpreting chart abbreviations TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 24
Note: see page 22 for details on interpreting chart abbreviations. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 25
Note: see page 22 for details on interpreting chart abbreviations. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Note: see page 22 for interpretation of abbreviations. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
*2: Approximate reading measured by digital multimeter on AC range. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
X 10 hrs Null Null Null Null Null Null Null Null Null TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 29
Dip Switches circuit board Min Button Max Button ADJ. Button TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
5. Refit the water heater front panel. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
G: Green O: Orange Y: Yellow Y/G: Yellow / Green TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
FAULT FINDING EZ-Link TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 33
DC2 –5V (or measurement by pulse counter of not less than 1310 pulses per minute) between 17 Blue and 16 Black TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 34
14 Green and 9 Black between 15 Blue and 9 Black TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 35
PCB between 11 Black and 12 Yellow TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 36
170V. between 1 Grey and Earth between 1 Black and 7 Red. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 37
Using an insulated tool, turn DIP switch 1 on the DIP switch or MIN and MAX buttons. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
PCB TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Remote controller failed – replace. (1E displayed?) PCB failed – replace. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Gas type connector was originally not redisplayed? inserted correctly. Faulty gas type connector - replace. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Replace the fan motor assembly. sent from the fan motor? Replace the PCB assembly. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Replace the igniter assembly, electrode or cable. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Clean the burner if necessary. Replace the burner change over assembly. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Replace the PCB assembly. information indicating 00? Replace flame sensors TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Replace the proportional gas flow regulating valve. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Remove the fault persists replace the controllers. water body assembly. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Turn hot tap off. Replace controller. operating light go out? Normal operation. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
* contact the Rheem Technical Helpline for assistance. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 49
Contact the Rheem Technical Helpline for assistance if fault remains. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
12. Refit the front panel to the water heater. label, no further adjustment is required. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 51
13. Refit the front panel to the water heater. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
13. Reassemble in reverse order of above. Replace gaskets if required. 14. Test for gas leaks using soapy water solution. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 53
6. Replace the felt gaskets (item 740) if required. 7. Test for gas leaks using soapy water solution. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 54
9. Test for gas leaks with soapy water solution. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 55
7. Reassemble in reverse order of above, replacing pipe O-rings and thermistor O-ring (item 432) if required. 8. Test for water leaks. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 56
TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 57
Bathroom Controllers: Disconnect the multi-pin plug. 5. Reassemble in reverse order of above. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 58
4. Disconnect remaining two connecting cord wiring loom plugs and remove connecting cord. 5. Reassemble in reverse order of above. TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
Page 59
(individual spare parts are not available, use complete EziSET kit 052310 when replacing parts). TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...
TM090 12-26 Series II CFGWH Service Instructions REV AB – Issued February 2019 This document is stored and maintained electronically by Rheem Technical Support. All printed copies are deemed “uncontrolled”...