Download Print this page

Jøtul F 105 R Installation And Operating Instructions Manual page 12

Advertisement

Available languages

Available languages

ENGLISH
Requirements for protection of wooden
fl ooring beneath the fi replace
The function of a fl oor plate is to protect the fl oor and
fl ammable materials against embers.
Jøtul F 105 with legs must have a fl oorplate below and in
front according to national standards and regulations.
Important! The space under the burnchamber of Jøtul F 105
with legs cannot be used for storage.
Jøtul recommends that any fl ooring made of combustible
material, such as linoleum, carpets, etc. should be removed
from under the fl oor plate.
Requirements for protection of
infl ammable fl oors in front of the
fi replace
The front plate must comply with national laws and regulations.
Contact your local building authorities regarding restrictions
and installation requirements.
3.3 Walls
Distance to walls made of combustible material - see fi g. 1
Distance to combustible wall protected by fi rewall: See
fi g. 1.
The fi replace may be used with an uninsulated fl ue pipe
provided the distances between the fi replace and walls made
of combustible materials are as shown in fi g. 1. Alternative
distances with shielded or insulated fl ue pipe are also
displayed in fi g. 1.
NB: Place the product in such a way that it is possible to clean
the stove, the fl ue pipe and the chimney passage.
Note! Ensure that furniture and other fl ammable materials
are not too close to the fi replace. Flammable materials
should not be placed within 900 mm of the fi replace.
NB: Make sure that furniture and other household items are
not so close as to get dried up by the stove.
12
Fresh air supply
The air used for combustion in any well-insulated house needs
to be replaced. This is particularly important in houses with
mechanical ventilation. Such replacement air can be procured
in several ways. The most important thing is to supply the air
to the room where the stove is placed. Place the outside wall
valve as close to the stove as possible and make sure that it
can be closed when the stove is not in use.
For the fresh air supply connection, follow the national and
local building regulations.
Closed combustion system
Use the stove's closed combustion system if you live in recently
built, airtight dwellings. Connect the external combustion air
through a ventilation pipe through the wall or the fl oor.
Air supply
The amount of combustion air for Jøtul's products is approximately
20-40 m 3 /h. The outside air connection may be fi tted directly to
the Jøtul F 105 through:
the bottom
through a fl exible supply hose from the outside/chimney
(only if the chimney has its own duct for external air) and to
the product's outside air connector.
Fig. 2A, through an outside wall
Fig. 2B, through the fl oor and ground plate

Advertisement

loading

This manual is also suitable for:

F 105 bF 105 llF 105 slF 105