Panasonic S-22MF2E5A8 Service Manual & Test Run Service Manual page 91

Vrf systems indoor unit
Table of Contents

Advertisement

3. Remote Controller Servicing Functions
Indoor unit sensors
00
Room temp. controlled*
01
Remote controller temp.
02
Indoor unit intake temp. (TA)
03
Indoor unit heat exchanger temp. E1 (E1)
04
05
Indoor unit heat exchanger temp. E3 (E3)
06
Discharge air temp. (BL)
07
Discharge air temp. setting
08
Indoor unit MOV pulse (MOV)
*Room temp. controlled: = Controlled room temperature
•When body thermostat controlled:
Controlled room temperature = Indoor unit intake temp. (TA) – Intake temperature shift (*1)
•Remote control thermostat controlled:
Controlled room temperature = Remote controller temp.
*1 Intake temperature shift: This is the shift value considered the temperature difference between the upper area
and lower area of the room in heating mode.
It is the value of the code "06" in the indoor unit's EEPROM setting.
Cooling mode: = 0
Outdoor unit sensors
* Refer to the Service Manual of Outdoor Unit.
5 - 55
VRF SYSTEMS Indoor Unit
5

Advertisement

Table of Contents
loading

Table of Contents