Panasonic S-22MF2E5A8 Service Manual & Test Run Service Manual page 42

Vrf systems indoor unit
Table of Contents

Advertisement

1. Simple Settings Function
Simple setting items
Item code
Filter sign ON time setting
01
(filter lifetime)
02
Degree of filter fouling
Filter sign ON times for each model
Model
data
4-Way cassette (U1, U2)
0001
4-Way cassette 60 × 60 (Y2)
Low Silhouette Ducted (F2)
0005
Slim Low Static Ducted (M1)
High Static Pressure
0006
Ducted (E2)
0007 Ceiling (T2)
0008 Wall Mounted (K1, K2)
NOTE
×
indicates that there is no corresponding filter.
indicates the filter sign ON time that is set at shipment.
150
• High fouling: Set when
5
Item
Changes the indoor unit filter lifetime when a high-performance filter or other
optional product is installed.
Reduces the filter sign ON time to 1/2 of the standard time (setting at the time of
shipping) for cases when filter fouling is more severe than normal.
Model
Standard
×
×
×
×
150
is selected for the degree of filter fouling (item code
Filter sign ON time
Standard
High fouling
Standard
2500
×
×
×
×
×
×
1500
75
×
5 - 6
VRF SYSTEMS Indoor Unit
Description
Long-life
High fouling
1250
×
×
750
×
Unit: hour
).