2. Detailed Settings Function
Item code
Item
Automatic drain pump
operation
Ventilation fan operation
Wired remote controller
sensor
"Operation change
control in progress"
display
OFF reminder function
for when weekly timer is
used
Discharge temperature
control
Heat exchanger
temperature for cold air
discharge
(Heat exchanger control
point for control to
prevent cold air)
Fan output switching
Drain pump delayed
stop time
Humidifier setting
Flap operation mode
Flap swing mode
No.
0000
No forced operation
0001
Forced operation for 1 minute
0060
Continuous operation
0000
None
0001
Ventilation fan operated by remote controller.
0000
Not used. (Body sensor is used.)
0001
Remote control sensor is used.
0000
Normal (displayed)
0001
Not displayed
0000
None
0001
Only stop time setting is enabled.
0000
Discharge temperature control OFF
0001
Discharge temperature control ON
0013
Control temperature 13°C
0014
Control temperature 14°C
0025
Control temperature 25°C
0026
Control temperature 26°C
0000
Output linked with fan. (ON when indoor unit fan is operating.)
0001
Fan mode operation output
0000
No delayed stop
0001
1 second delayed stop
0002
2 seconds delayed stop
0058
58 seconds delayed stop
0059
59 seconds delayed stop
0060
60 seconds delayed stop
0000
Humidifier output OFF. Drain pump stopped.
0001
Humidifier output ON. Drain pump operates.
Humidifier output ON. Drain pump operates for 1 minute when total humidifier
0002
operating time reaches 60 minutes.
0003
Humidifier output ON. Drain pump stopped.
0000
Standard setting
0001
Draft reduction mode (Flap lower-limit position is shifted upwards.)
0000
Smudging reduction mode (Flap swing upper-limit position is shifted downwards.)
0001
Normal mode
0002
Draft reduction mode (Flap swing lower-limit position is upwards.)
5 - 17
VRF SYSTEMS Indoor Unit
Setting data
Description
1 minute delayed stop
Except
2 minutes delayed stop
Indoor unit
Type
58 minutes delayed stop
U1, U2, Y2,
59 minutes delayed stop
F2, T2, E2
60 minutes delayed stop
Indoor
unit
Type
U1, U2, Y2,
F2, T2, E2