Air Balance; Power Exhaust Specifications - York MagnaDRY DK-07 Series Installation Manual

Single package air conditioners and single package gas/electric units
Table of Contents

Advertisement

335224-BIM-B-1208
TABLE 32: POWER EXHAUST SPECIFICATIONS
POWER EXHAUST
MODEL
2PE0473125
208/230
2PE0473146
2PE0473158
*.
Motors are multi-tapped and factory-wired for high speed.
Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air
distribution throughout the conditioned space. The job specifications may require that this balancing be done by someone other
than the equipment installer.
44
VOLT
PHASE
HP
1
460
1
0.75
575
1

AIR BALANCE

Belt drive blower systems MUST be adjusted to the
specific static and CFM requirements for the appli-
cation. The Belt drive blowers are NOT set at the
factory for any specific static or CFM. Adjustments of
the blower speed and belt tension are REQUIRED.
Tighten blower pulley and motor sheave set screws
after these adjustments. Re-checking set screws
after 10-12 hrs. run time is recommended.
MOTOR
*
QTY
LRA
RPM
24.9
1075
1
N/A
1050
ELECTRICAL
FUSE
SIZE
FLA
MCA
5.0
6.3
10
2.2
2.8
1.5
1.9
Johnson Controls Unitary Products
CFM @
0.1 ESP
5
3,800
4