Bryant 800SB Operating Instructions Manual page 19

80% afue, single stage, multi-speed ecm, 4-way multipoise, non–condensing gas furnace
Table of Contents

Advertisement

800SB/801SB: Installation, Start–Up, Operating and Service and Maintenance Instructions
Fig. 30 – Chimney Inspection Chart
Masonry Chimney Requirements
NOTE: These furnaces are CSA design-certified for use in exterior
tile-lined masonry chimneys with a factory accessory Chimney Adapter
Kit. Refer to the furnace rating plate for correct kit usage. The Chimney
Adapter Kits are for use with ONLY furnaces having a Chimney Adapter
Kit numbers marked on the furnace rating plate.
If a clay tile-lined masonry chimney is being used and it is exposed to
the outdoors below the roof line, relining might be required. Chimneys
shall conform to the Standard for Chimneys, Fireplaces, Vents, and Solid
Fuel Burning Appliances current edition of ANSI/NFPA 211 and must
be in good condition.
U.S.A.— Refer to Sections 13.1.8 and 13.2.20 of the current edition of
NFGC NFPA54/ANSI Z223.1 or the authority having jurisdiction to
determine whether relining is required. If relining is required, use a
properly sized listed metal liner, Type-B vent, or a listed alternative
venting design.
NOTE: See the current edition of NFPA54/ANSI Z223.1, 13.1.8 and
13.2.20 regarding alternative venting design and the Exception, which
cover installations such as the Chimney Adapter Kits, which are listed
for use with these furnaces. See Product Data Sheet for accessory listing.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected
to the venting system being placed into operation could result in carbon
monoxide poisoning or death.
The following steps shall be followed for each appliance connected to
the venting system being placed into operation, while all other
appliances connected to the venting system are not in operation:
-
Seal any unused openings in venting system.
-
Inspect the venting system for proper size and horizontal pitch,
as required in the current edition of National Fuel Gas Code,
ANSI Z223.1/NFPA 54 and these instructions. Determine that
there is no blockage or restriction, leakage, corrosion and other
deficiencies, which could cause an unsafe condition.
-
As far as practical, close all building doors and windows and all
doors between the space in which the appliance(s) connected to
the venting system are located and other spaces of the building.
-
Close fireplace dampers.
-
Turn on clothes dryers and any appliance not connected to the
venting system. Turn on any exhaust fans, such as range hoods
and bathroom exhausts, so they are operating at maximum
speed. Do not operate a summer exhaust fan.
-
Follow the lighting instructions. Place the appliance being
inspected into operation. Adjust the thermostat so appliance is
operating continuously.
-
Test for spillage from draft hood equipped appliances at the
draft hood relief opening after 5 minutes of main burner
operation. Use the flame of a match or candle.
-
If improper venting is observed during any of the above tests,
the venting system must be corrected in accordance with the
current edition of National Fuel Gas Code, ANSI Z223.1/NFPA
54.
A10133
-
After it has been determined that each appliance connected to
the venting system properly vents when tested as outlined
above, return doors, windows, exhaust fans, fireplace dampers
and any other gas-fired burning appliance to their previous
conditions of use.
The Chimney Adapter Kit is listed alternative venting system for these
furnaces. See the kit instructions for complete details.
This furnace is permitted to be vented into a clay tile-lined masonry
chimney that is exposed to the outdoors below the roof line, provided:
1. Vent connector is Type-B double-wall, and
2. This furnace is common vented with at least 1 draft hood equipped
appliance, and
3. The combined appliance input rating is less than the maximum
capacity given in
4. The input rating of each space heating appliance is greater than the
minimum input rating given in
Design Temperature. Chimneys having internal areas greater than
38 square inches require furnace input ratings greater than the input
ratings of these furnaces. See footnote at bottom of
5. The authority having jurisdiction approves.
19
WARNING
!
Table
7, and
Table 8
for the local 99% Winter
Table
8, and

Advertisement

Table of Contents
loading

This manual is also suitable for:

801sb

Table of Contents