6.1.4

Update time of the I/O data

You can estimate the typical update time for an I/O cycle as follows:
    Update time (can be set starting at 2 ms)
    + I/O processing (typically 1.4 ms, +/- 1 ms jitter due to free-running cycles)
    + EM conversion (dependent on cycle time and parameter assignment of the module)
If necessary, you must take into account other influences caused by the MTCP client and
network components by adding them.
6.1.5

Address space

The DI 16x24VDC M12‑L 8xM12 I/O device can be configured differently; see following table.
Depending on the configuration, additional/different addresses are assigned in the process
image input.
Configuration options of the DI 16x24VDC M12‑L 8xM12 I/O device
When the I/O device is configured using a GSD file, the configurations are available under
different short designations/device names in the device view of MFCT.
The following configurations are possible:
Table 6-2  Configuration options
Configuration
1 x 16-channel DI 16x24VDC
1 x 16-channel DI 16x24VDC QI
1 x 16-channel DI 16x24VDC MSI
I/O device digital inputs DI 16x24VDC M12-L 8xM12 (6ES7141-6BH00-0BB0)
Equipment Manual, 03/2023, A5E46570510-AD
6.1 Functions/parameters/address space
Short designation/
device name in the
GSD file (device view in the
configuration software)
DI 16x24VDC
DI 16x24VDC QI
DI 16x24VDC MSI
Modbus TCP
Configuration software,
e.g. with MFCT
GSD file in
MFCT V1.3 SP1 or higher
X
X
X
47