CONDENSATE DRAIN CONNECTION
The unit is supplied with a drain connection to connect the drain
piping. When installing condensate piping, follow these
recommendations:
S
Condensate piping should slope downward in the
direction of the condensate flow, with a minimum
gradient of 1 in. per 100 inches.
S
When multiple units are connected to a common
condensate drain, ensure the drain is large enough to
accommodate the volume of condensate from all units. It
is also recommended to place an air vent in the condensate
piping to prevent any air locks.
S
Condensate piping must not be installed where it may be
exposed to freezing temperatures.
Insulating
Downward declivity
material
lower than 1/100
Put as deep as possible
(about 10cm)
Downward declivity
lower than 1/100
Fig. 21 - Condensate Flow
1.5m~2m
Bend
S shape
VP30
ELECTRICAL CONNECTIONS SIZES 09−12
1. Remove the installation bearer of the sensing device (see
Fig. 22).
Fig. 22 - Remove installation bearer
2. Remove the Electrical Cover.
3. Connect wiring from the outdoor unit per the connection
diagram (see Fig. 25).
4. Reinstall the Electrical Cover and sensing device bearer.