Inverter Rating - Mitsubishi Electric FR-A802-P Instruction Manual

Separated converter type for parallel operation
Table of Contents

Advertisement

Inverter rating

6.1
Inverter rating
Model FR-A842-[ ]-P
Applicable motor capacity (kW)
Rated capacity (kVA)

Rated current (A)

Overload current rating

Rated voltage

Regenerative braking torque
(When the converter unit is used)
DC power supply voltage
Control power supply auxiliary input
Permissible control power supply auxiliary input fluctuation Frequency 5%, voltage 10%
Protective structure (IEC 60529)
Cooling system
Approx. mass (kg)


The rated output capacity indicated assumes that the output voltage is 440 V.

Total output current of the inverters operated in parallel

The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty,
allow time for the inverter and motor to return to or below the temperatures under 100% load.

The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range.
However, the maximum point of the voltage waveform at the inverter output side is the power supply voltage multiplied by about

ND rating reference value

For the power voltage exceeding 480 V, set Pr.977 Input voltage mode selection. (For details, refer to the FR-A800 Instruction Manual
(Detailed).)

FR-DU08: IP40 (except for the PU connector section)

Total mass of the inverters operated in parallel

When a multi-wound motor is driven by two inverters in parallel with "10200 or 10201" set in Pr.1001 under Real sensorless vector control or
Vector control, values in the following table are applied.
Applicable motor capacity (kW)
Rated capacity (kVA)
Rated current (A)
106
SPECIFICATIONS
LD

ND (initial setting)
LD
ND (initial setting)
LD
ND (initial setting)
LD
ND (initial setting)

Maximum brake torque 10% torque/continuous

Model FR-A842-[ ]-P
LD
ND (initial setting)
LD
ND (initial setting)
LD
ND (initial setting)
Single unit
Two in parallel
400K 450K 500K 400K 450K 500K 400K 450K 500K
09620 10940 12120 09620 10940 12120 09620 10940 12120
450
500
560
710
400
450
500
630
660
733
834
1056
587
660
733
939
866
962
1094
1386
770
866
962
1232
120% 60 s, 150% 3 s (inverse-time characteristics) at surrounding air
temperature of 50°C
150% 60 s, 200% 3 s (inverse-time characteristics) at surrounding air
temperature of 50°C
Three-phase 380 to 500 V
430 to 780 VDC
Single phase 380 to 500 V 50/60 Hz
Open type (IP00)
Forced air cooling
243
243
243
486
Two in parallel
400K 450K 500K
09620 10940 12120
900
945
1065
800
900
945
1320
1466
1668
1174
1320
1466
1732
1924
2188
1540
1732
1924
Three in parallel
800
900
1065
1200
710
800
945
1065
1173
1334
1584
1759
1056
1173
1409
1584
1539
1750
2078
2309
1386
1539
1848
2078

486
486
729
729
1350
1200
2002
1759
2626
2309
729
.

Advertisement

Table of Contents
loading

Table of Contents