Charging refrigerant (in manual additional refrigerant charge
mode)
The remaining additional refrigerant charge can be charged by
operating the outdoor unit by means of the manual additional
refrigerant charge mode.
5 Connect as shown. Make sure valve A is closed.
p <
p >
A
d
b
R410A
a
c
a
Weighing scales
b
Refrigerant R410A tank (siphon system)
c
Vacuum pump
d
Refrigerant charge port
A
Valve A
NOTICE
The refrigerant charging port is connected to the piping
inside the unit. The unit's internal piping is already factory
charged with refrigerant, so be careful when connecting
the charge hose.
6 Open all outdoor unit stop valves. At this point, valve A must
remain closed!
7 Take all the precautions mentioned in
page 15
and
"7 Commissioning" on page 20
8 Turn on the power of the indoor units and outdoor unit.
9 Activate setting [2‑20] to start the manual additional refrigerant
charge mode. For details, see
page 17.
Result: The unit will start operation.
INFORMATION
The manual refrigerant charge operation will automatically
stop within 30 minutes. If charging is not completed after
30 minutes, perform the additional refrigerant charging
operation again.
INFORMATION
▪ When a malfunction is detected during the procedure
(e.g., in case of closed stop valve), a malfunction code
will be displayed. In that case, refer to
codes when charging refrigerant"  on page  13
solve the malfunction accordingly. Resetting the
malfunction can be done by pushing BS3. You can
restart the "Charging" instructions.
▪ Aborting the manual refrigerant charge is possible by
pushing BS3. The unit will stop and return to idle
condition.
10 Open valve A.
11 Charge refrigerant until the remaining determined additional
refrigerant amount is added, and then close valve A.
12 Press BS3 to stop the manual additional refrigerant charge
mode.
NOTICE
Make sure to open all stop valves after (pre-) charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
RXYSCQ4~6TMV1B
VRV IV-S system air conditioner
4P555881-1 – 2019.07
d
"6  Configuration"  on
into account.
"6.1.8 Mode 2: Field settings" on
"5.6.4  Error
and
NOTICE
After adding the refrigerant, do not forget to close the lid of
the refrigerant charging port. The tightening torque for the
lid is 11.5 to 13.9 N•m.
5.6.4

Error codes when charging refrigerant

INFORMATION
If a malfunction occurs, the error code is displayed on the
user interface of the indoor unit.
If a malfunction occurs, close valve A immediately. Confirm the
malfunction code and take corresponding action,
problems based on error codes" on
5.6.5
To fix the fluorinated greenhouse gases
label
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
1
=
f
GWP: XXX
=
2
2
1
+
1
2
=
GWP × kg
=
1000
a
If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Quantity of fluorinated greenhouse gases of the total
refrigerant charge expressed as tonnes CO
f
GWP = Global warming potential
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO
2
Formula to calculate the quantity in CO
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge
label. That GWP is based on the current legislation on
fluorinated greenhouse gases. The GWP mentioned in the
manual might be outdated.
2 Fix the label on the inside of the outdoor unit. There is a
dedicated place for it on the wiring diagram label.
5.7

Connecting the electrical wiring

5.7.1

Field wiring: Overview

Field wiring consists of power supply (always including earth) and
indoor-outdoor communication (= transmission) wiring.
Example:
5 Installation
"8.1  Solving
page 21.
a
kg
b
kg
c
d
kg
e
tCO
eq
2
equivalent.
2
equivalent.
equivalent
2
Installation and operation manual
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxyscq4tmv1bVrv iv-s seriesRxyscq6tmv1bRxyscq-tv1

Table of Contents