16 Electrical installation

INFORMATION
▪ When a malfunction is detected during the procedure
(e.g., in case of closed stop valve), a malfunction code
will be displayed. In that case, refer to
codes when charging
malfunction accordingly. Resetting the malfunction can
be done by pushing BS3. You can restart the
"Charging" instructions.
▪ Aborting the manual refrigerant charge is possible by
pushing BS3. The unit will stop and return to idle
condition.
10 Open valve A.
11 Charge refrigerant until the remaining determined additional
refrigerant amount is added, and then close valve A.
12 Press BS3 to stop the manual additional refrigerant charge
mode.
NOTICE
Make sure to open all stop valves after (pre-) charging the
refrigerant.
Operating with the stop valves closed will damage the
compressor.
NOTICE
After adding the refrigerant, do not forget to close the lid of
the refrigerant charging port. The tightening torque for the
lid is 11.5 to 13.9 N•m.
15.4
Error codes when charging
refrigerant
INFORMATION
If a malfunction occurs, the error code is displayed on the
outdoor unit's 7‑segments display and on the user interface
of the indoor unit.
If a malfunction occurs, close valve A immediately. Confirm the
malfunction code and take corresponding action,
codes" [ 4  39].
problems based on error
15.5
To fix the fluorinated greenhouse
gases label
1 Fill in the label as follows:
Contains fluorinated greenhouse gases
RXXX
=
1
f
GWP: XXX
2
=
2
1
+
1
2
=
GWP × kg
=
1000
a
If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of a.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e
Quantity of fluorinated greenhouse gases of the total
refrigerant charge expressed as tonnes CO
f
GWP = Global Warming Potential
Installation and operation manual
30
"15.4  Error
refrigerant"  [ 4   30] and solve the
"20.1  Solving
a
kg
b
kg
c
d
kg
e
tCO
eq
2
equivalent.
2
NOTICE
Applicable legislation on fluorinated greenhouse gases
requires that the refrigerant charge of the unit is indicated
both in weight and CO
2
Formula to calculate the quantity in CO
tonnes: GWP value of the refrigerant × total refrigerant
charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge
label.
2 Fix the label on the inside of the outdoor unit. There is a
dedicated place for it on the wiring diagram label.
15.6
To check for refrigerant leaks after
charging
All field made refrigerant joints must be tested for tightness.
No leak shall be detected with a test method that has a sensitivity of
5  grams refrigerant per year or better, at a pressure of at least
0.25  times the maximum working pressure (see "PS High" on the
unit name plate).
In case a leak is detected
1 Recover the refrigerant and repair the joint(s).
2 Perform the leak tests see
"14.3.2 To perform a leak
3 Charge refrigerant.
4 Check for refrigerant leaks after charging (see above).
16
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
national wiring regulation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction
MUST
legislation.
WARNING
The appliance MUST be installed in accordance with
national wiring regulations.
WARNING
ALWAYS use multicore cable for power supply cables.
16.1

About electrical compliance

This equipment complies with:
▪ EN/IEC 61000‑3‑12 provided that the short-circuit power S
greater than or equal to the minimum S
point between the user's supply and the public system.
▪ EN/IEC
61000‑3‑12
=
Standard setting the limits for harmonic currents produced by
equipment connected to public low-voltage systems with input
current >16 A and ≤75 A per phase.
▪ It is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected ONLY to a supply
with a short-circuit power S
minimum S
value.
sc
equivalent.
equivalent
2
test" [ 4  27].
comply
with
the
applicable
value at the interface
sc
European/International
Technical
greater than or equal to the
sc
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600329-1E – 2023.02