Routing through
the frame
b
a
a Power supply cable
b Transmission wiring cable
Connecting to the
When cables are routed from the unit, a
frame
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.
When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.
A Inside of the outdoor unit
B Outside of the outdoor unit
a Wire
b Bush
c Nut
d Frame
e Hose
6 Reattach the service cover.
7 Connect an earth leakage circuit breaker and fuse to the power
supply line.
5.8
Finishing the outdoor unit
installation
5.8.1

To finish the transmission wiring

After installing the transmission wires inside the unit, wrap them
along with the on-site refrigerant pipes using finishing tape, as
shown in figure below.
a
c
b
e
d
a
Liquid pipe
b
Gas pipe
c
Insulator
d
Transmission wiring (F1/F2)
e
Finishing tape
6

Configuration

INFORMATION
It is important that all information in this chapter is read
sequentially by the installer and that the system is
configured as applicable.
RXYSCQ4~6TMV1B
VRV IV-S system air conditioner
4P555881-1 – 2019.07
A B
a b c
d
e
DANGER: RISK OF ELECTROCUTION
6.1

Making field settings

6.1.1

About making field settings

To configure the heat pump system, you must give input to the
outdoor unit's main PCB (A1P). This involves the following field
setting components:
▪ Push buttons to give input to the PCB
▪ A display to read feedback from the PCB
Field settings are defined by their mode, setting and value. Example:
[2‑8]=4.
PC configurator
For VRV IV-S heat pump system it is alternatively possible to make
several commissioning field settings through a personal computer
interface (for this, option EKPCCAB is required). The installer can
prepare the configuration (off-site) on PC and afterwards upload the
configuration to the system.
See also:
"6.1.9  To connect the PC configurator to the outdoor
unit" on
page 20.
Mode 1 and 2
Mode
Mode 1
Mode 1 can be used to monitor the current
situation of the outdoor unit. Some field setting
(monitoring
contents can be monitored as well.
settings)
Mode 2
Mode 2 is used to change the field settings of
the system. Consulting the current field setting
(field settings)
value and changing the current field setting
value is possible.
In general, normal operation can be resumed
without special intervention after changing field
settings.
Some field settings are used for special
operation (e.g., 1 time operation, recovery/
vacuuming setting, manual adding refrigerant
setting, etc.). In such a case, it is required to
abort the special operation before normal
operation can restart. It will be indicated in
below explanations.
6.1.2

To access the field setting components

See
"5.1.1 To open the outdoor unit" on
6.1.3

Field setting components

NOTICE
The DIP switch (DS1 on A1P) is not used. Do NOT change
the factory setting.
The components to make field settings are as follows:
TEST:
MODE
HWL:
A1P
H1P
H2P
BS1
MODE
BS1~BS5
Push buttons
H1P~H7P
7‑LEDs display
H8P
LED for indication during initialisation
ON ( ) OFF ( ) Flashing ( )
6 Configuration
Description
page 8.
C/H SELECT
L.N.O.P. DEMAND
MULTI
IND
MASTER SLAVE
H3P
H4P
H5P
H6P
H7P
H8P
BS2
BS3
BS4
BS5
SET
RETURN
TEST
RESET
Installation and operation manual
15