58TP0A/58TP1A: Installation, Start-up, Operating and Service and Maintenance Instructions
The thermostat anticipator should NOT be in the circuit while
measuring current.
(1.) Set SW1-2 switch on furnace control board to ON.
(2.) Remove thermostat from subbase or from wall.
(3.) Connect an amp. meter across the R and W subbase
terminals or R and W wires at wall. (See
Fig. 52 – Amp. Draw Check with Ammeter
(4.) Record amp. draw across terminals when furnace is in low
heat and after blower starts.
(5.) Set heat anticipator on thermostat per thermostat
instructions and install on subbase or wall.
(6.) Turn SW1-2 switch OFF.
(7.) Install blower access door.
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.
9. Set Airflow for Air Conditioning -Single Stage and High Stage
Cooling.
The ECM blower can be adjusted for a range of airflow for Low
Speed or High Speed cooling. See
(With Filter).
The cooling airflow is adjusted by turning Setup switches SW2-6,
SW2-7 and SW2-8 either ON or OFF. Select the required airflow.
(See
Fig.
55).
NOTE: 5.5 ton airflow will truncate at 2200 cfm on applicable models.
For a complete explanation of cooling airflow, refer to the section titled
"Sequence of Operation."
10. The Continuous Fan airflow selection via Setup switches SW2-3,
SW2-4, SW2-5 is also the switch setting for low-speed cooling
when the furnace is used with a two-speed cooling or heat pump
unit. Refer to the Adjustments section (also
setup switch configurations. This setup feature allows continuous
fan airflow or low-cooling airflow to be adjusted.
The continuous fan speed can be further adjusted at the thermostat
using the Continuous Blower Speed Selection from Thermostat
function. Changing the continuous fan speed at the thermostat
DOES NOT change the low speed cooling airflow selected at the
control board. See the section titled Continuous Blower Speed
Selection from Thermostat in the Sequence of Operation section of
this document.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Fig.
52.
A96316
Table
12-Air Delivery - CFM
Fig. 54
and
Fig.
55) for
Table 10 – Gas Rate (CU ft./hr)
SIZE OF TEST DIAL
SECONDS G
FOR 1 REV
1 Cu
2 Cu
Ft.
Ft.
10
360
720
11
327
655
12
300
600
13
277
555
14
257
514
15
240
480
16
225
450
17
212
424
18
200
400
19
189
379
20
180
360
21
171
343
22
164
327
23
157
313
24
150
300
25
144
288
26
138
277
27
133
267
28
129
257
29
124
248
30
120
240
31
116
232
32
113
225
33
109
218
34
106
212
35
103
206
36
100
200
37
97
195
38
95
189
39
92
185
40
90
180
41
88
176
42
86
172
43
84
167
44
82
164
45
80
160
46
78
157
47
76
153
48
75
150
49
73
147
29
SIZE OF TEST
DIAL
SECONDS
FOR 1 REV
5 Cu
1 Cu
2 Cu
Ft.
Ft.
Ft.
1800
50
72
144
1636
51
71
141
1500
52
69
138
1385
53
68
136
1286
54
67
133
1200
55
65
131
1125
56
64
129
1059
57
63
126
1000
58
62
124
947
59
61
122
900
60
60
120
857
62
58
116
818
64
56
112
783
66
54
109
750
68
53
106
720
70
51
103
692
72
50
100
667
74
48
97
643
76
47
95
621
78
46
92
600
80
45
90
581
82
44
88
563
84
43
86
545
86
42
84
529
88
41
82
514
90
40
80
500
92
39
78
486
94
38
76
474
96
38
75
462
98
37
74
450
100
36
72
439
102
35
71
429
104
35
69
419
106
34
68
409
108
33
67
400
110
33
65
391
112
32
64
383
116
31
62
375
120
30
60
367
5 Cu
Ft.
360
355
346
340
333
327
321
316
310
305
300
290
281
273
265
257
250
243
237
231
225
220
214
209
205
200
196
192
188
184
180
178
173
170
167
164
161
155
150

Advertisement

Table of Contents
loading

This manual is also suitable for:

58tp0aA series

Table of Contents