1. Change the related functions of the controller through adjusting the parameters, refer to table 1.
2. The wired controller parameter includes two codes "XY", the first code "X" means function class, the second code "Y" means detailed configuration of this function.
3. Setting method:
Simultaneously press and hold "Mode" and "Fan" buttons of the wired controller for 5 seconds to enter the parameter settings;
1
The value of this first code "X" is "0", press the temperature setting button
2
After setting the second code value, press
3
When the first code value is "6",
4
4. Theses parameters have been factory set and may not need to be adjusted.
Table 1
First code
Function
Cool-only/ Cool-Heat
0
selection
Indoor unit
1
communication address
setting
2
Power-off memory
3
Filter cleaning reminding
Remote receiving
5
function
Centigrade/Fahrenheit
6
display
CLIMATE 5000 VRF
button to switch the first code to the next value;
press button again to exit the parameters setting.