FAULT WARNINGS CONDITION

All active Fault Warnings events will appear on the display and
can also be listed by selecting the active Fault summary icon
. The Fault LED is lit and the Buzzer sounds to give an audible
announcement.
FAULT
SILENCE-RESOUND
MUTE BUZZER
RESET
Mute Buzzer
INSPIRE E10/E15 Control Panels - Operating instructions
What do I need to do?
01
02
03
04
05
To silence the panel buzzer sound,
select the 'MUTE BUZZER' button
.
Where there are many active events
listed use the Search
locate the exact event(s) of interest
or view.
Expand a fault view by selecting
the down arrow icon
. If device
disablement is required then select
the 'Disable Device'
You can view further information
about a fault event by selecting the
'More Info' button
. The previous
associated fault history can be
viewed here
. On selecting the
down-arrow icon
you can view
information about the device having
a fault.
By selecting the 'Cause and
Solution'
tab you can investigate
the fault and find solutions to repair
the fault. Log in with your Access
level 2 password. Select the 'RESET'
button to clear repaired faults.
facility to
button.
23