12-6. ROTATION SETTING
Setting method of each function by wired remote controller
■ PAR-4xMAA ("x" represents 1 or later)
Stop operation
Select "Service" from the Main menu, and press the [
Select "Settings" with the F1 or F2 button, and press the [
Select "Rotation setting" with the F1 or F2 button, and press the [
ton.
Set the rotation function.
Select "Rotation" with the F1 button.
•
Select the rotation period or "Backup only" with the F2 or F3 button.
•
■ "Rotation" setup
None, 1 day, 3 days, 5 days, 7 days, 14 days, 28days, Backup only
Notes:
When 1 to 28 days are selected, the backup function is also enabled.
•
When "Backup only" is selected, the rotation function will be disabled. The sys-
•
tems with refrigerant addresses of 00 or 01 (00 system/ 01 system) will be oper-
ated as a main system while the 02 system is the standby mode as backup.
Set the support function.
Select "TempDifTrigger" with the F1 button.
•
Select "the difference between the suction temperature and the set temperature"
•
with the F2 or F3 button.
■ "TempDifTrigger" setup
None, +4ºC, +6ºC, +8ºC
Notes:
The support function is available only in the COOL mode. (Not available in the
•
HEAT, DRY and AUTO mode.)
The support function is enabled when any option other than "None" is selected
•
from the "Rotation" setup.
Update the setting.
Press the [
] button to update the setting.
•
Reset method
Press the F4 button in step
•
start from the 00 or 01 systems.
Note: When the 02 system is in the backup operation, the 00 or 01 systems will be operated again.
OCH753A
] button.
or
to reset the operation time of the rotation function. Once it is reset, operation will
45
Function setting
Rotation setting
Service menu:
] button.
F1
]
but-
Rotation
TempDifTrigger
Select :
Cur.
F1
Rotation
TempDifTrigger
Select :
Cur.
F1
Settings menu
Cursor
F2
F3
F4
Rotation setting
Backup only
+4°C
− Content +
R
e
s
t e
F2
F3
F4
Rotation setting
Backup only
+4°C
− Content +
R
e
s
t e
F2
F3
F4