Mitsubishi Electric Mr. SLIM PCA-M71HA2 Service Manual page 25

Split-type, heat pump air conditioners; split-type, air conditioners
Table of Contents

Advertisement

OPERATING PROCEDURE
4. Removing the fan motor
(1) Remove the oil filter. (See Figure 1)
(2) Remove the control box cover. (See Photo 2)
(3) Remove the room temperature thermistor connector (CN20)
on the indoor controller board. (See Photo 3)
(4) Remove a filter rail that is the nearest to the control box.
(See Photo 4)
(5) Remove the fan guard. (See Photo 5)
(6) Remove the room temperature thermistor together with the
holder at the right side of the casing.
5. Removing the fan motor and the sirocco fan
(1) Remove the oil filter. (See Figure 1)
(2) Remove the control box cover. (See Photo 2.)
(3) Remove the fan motor relay connectors (6P) in the control
box. (See Photo 3)
(4) Remove the 2 filter rails. (See Photo 1, 4)
(5) Remove the fan guard. (See Photo 5)
(6) Remove the lower casing. (See Photo 6)
(7) Remove the green earth wire from the motor support.
(See Photo 7)
(8) Remove the 2 screws (M5 × 12) for motor support, and
remove the left and right motor supports.
(9) Remove the fan motor together with the sirocco fan.
(10) Remove the 2 set screws (M6) to separate the fan
motor from the sirocco fan.
OCH753A
PHOTOS/FIGURES
Photo 4
Screws for
filter rail
Photo 5
Room
Control box
temperature
cover
thermistor
Photo 6
Screws for casing
Control box
Casing
cover
Photo 7
Earth wire
Sirocco fan
25
25
Room temperature
thermistor
Screws for Fan guard
Screws for Fan guard
Screws for casing
Casing
Fan motor
Set screws
Screws for
Motor
motor support
support
Filter rail
Fan guard
Sirocco fan

Advertisement

Table of Contents
loading