Table 4 - Power Applied, By Module Type - Honeywell 900U02-0100 User And Installation Manual

Process & safety controller
Table of Contents

Advertisement

Module
Controller C30 and C30S
Controller C50 and C50S
Controller C70 and C70S
Controller C75 and C75S
Redundancy switch module (RSM)
Power Status Module (PSM)
Scanner 1 Port (S50/S50S)
Scanner 2 Port (S75/S75S)
Analog Input (Universal)
Analog Input (High level)
Analog Output (4 points)
Analog Output (8 pts. internal 24V)
Analog Output (8 pts. external 24V)
Analog Output (16 pts. internal 24V)
Analog Output (16 pts. external 24V)
Contact Input
Relay Output
16 pt DC In (@ 24V)
16 pt DC In (@ 32V)
32 pt DC In (@ 24V)
32 pt DC In (@ 32V)
16 pt DC Out
32 pt DC Out
AC In (@120V)
AC In (@240V)
AC/DC In
AC Out
PFQ
Universal IO (16 Pts)
Revision 10
ControlEdge HC900 Process & Safety Controller User and Installation Manual
May 2019
Table 4 – Power Applied, by Module Type
ControlEdge
HC900 Hardware
Power (Watts)
6.0
6.0
7.1
7.8
0.1
0.1
3.9
5.0
0.8
1.6
5.1
9.4
1.1
18.3
1.7
1.6
3.0
0.7
0.7
1.1
1.1
1.7
1.2
0.7
0.7
0.7
1.1
6.7
2.45
Field Power
Total Power
(Watts)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
8.3
0.0
16.6
0.0
0.0
2.6
5.1
3.1
5.1
1.2
1.8
1.9
7.7
7.7
12.0
0.1
4.5
(Watts)
6.0
6.0
7.1
7.8
0.1
0.1
3.9
5.0
0.8
1.6
5.1
9.4
9.4
18.3
18.3
1.6
3.0
3.3
5.7
4.2
6.2
2.9
3.0
2.6
8.3
8.3
13.1
6.8
6.95
57