Figure 8. Equipment in Confined Space - All Air from
Roof Terminated
Exhaust Pipe
* See Maximum Vent Lengths table
NOTE-The inlet and outlet air openings shall each have a
free area of at least one square inch per 4,000 Btu (645mm
per 1.17kW) per hour of the total input rating of all equipment
in the enclosure.
Figure 9. Equipment in Confined Space
(Inlet Air from Ventilated Attic and Outlet Air to
When ducts are used, they shall be of the same cross-
sectional area as the free area of the openings to which
they connect. The minimum dimension of rectangular
air ducts shall be no less than 3 inches (75 mm). In
calculating free area, the blocking effect of louvers, grilles,
or screens must be considered. If the design and free area
of protective covering is not known for calculating the size
opening required, it may be assumed that wood louvers
will have 20 to 25 percent free area and metal louvers and
grilles will have 60 to 75 percent free area. Louvers and
grilles must be fixed in the open position or interlocked
with the equipment so that they are opened automatically
during equipment operation.
507266-05
Outside
Ventilation Louvers
Inlet Air
(Minimum 12 in.
(305mm) above
Attic Floor)
*Intake Debris
Screen
(Provided)
Furnace
Outside)
Roof Terminated
Exhaust Pipe
Ventilation
Louvers
(Crawl Space)
NOTE-The inlet and outlet air openings shall each have a
free area of at least one square inch per 4,000 Btu (645mm
per 1.17kW) per hour of the total input rating of all equipment
in the enclosure.
Figure 10. Equipment in Confined Space
(Inlet Air from Ventilated Crawlspace and Outlet Air to
Shipping Bolt Removal
Units with 1/2 hp blower motor are equipped with three
flexible legs and one rigid leg. The rigid leg is equipped
with a shipping bolt and a flat white plastic washer (rather
than the rubber mounting grommet used with a flexible
mounting leg). See Figure 11. The bolt and washer must
be removed before the furnace is placed into operation.
After the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
2
Issue 1933
12 in. (305mm)
Furnace
above Crawl
Space Floor
Coupling or
*Intake Debris Screen Provided
3 in. to 2 in.
Transition
(Field Provided)
* See Maximum Vent Lengths table
Outside)
Units with 1/2 HP
Figure 11.
Inlet Air
Minimum
2
Blower Motor
Page 9 of 58