Lennox 95G2UHV Installation Instructions Manual page 21

Warm air gas furnace upflow/horizontal left air discharge direct vent & non-direct vent
Table of Contents

Advertisement

Maximum Allowable Exhaust Vent Lengths with Furnace Installed in a Closet or Basement Using Ventilated Attic or Crawl
1-1/2" Pipe
Number
of 90°
Capacity
Elbows
Used
45
70
90
1
20
15
2
15
10
3
10
4
5
n/a
6
n/a
7
n/a
8
9
10
1-1/2" Pipe
Number
of 90°
Capacity
Elbows
Used
45
70
90
1
20
15
2
15
10
3
10
4
5
n/a
6
n/a
7
n/a
8
9
10
* Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake and
Exhaust must be same pipe size.
* Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent length
calculation.
507266-05
Space for Intake Air in Feet
Standard Termination at Elevation 0 - 4,500 ft
2" Pipe
Capacity
110
135
45
70
90
66
51
29
61
46
24
56
41
19
51
36
14
46
31
9
n/a
n/a
41
26
4
36
21
31
16
n/a
26
11
21
6
Standard Termination at Elevation 4,501 - 10,000 ft
2" Pipe
Capacity
110
135
45
70
90
66
51
29
61
46
24
56
41
19
51
36
14
46
31
9
n/a
n/a
41
26
4
36
21
31
16
n/a
26
11
21
6
2-1/2" Pipe
Capacity
110
135
45
70
90
9
95
95
73
4
90
90
68
85
85
63
80
80
58
75
75
53
n/a
70
70
48
n/a
65
65
43
60
60
38
55
55
33
50
50
28
2-1/2" Pipe
Capacity
110
135
45
70
90
95
95
73
90
90
68
85
85
63
80
80
58
75
75
53
n/a
n/a
70
70
48
65
65
43
60
60
38
55
55
33
50
50
28
Table 5C.
Issue 1933
3" Pipe
Capacity
110
135
45
70
90
38
113
112
93
33
108
107
88
28
103
102
83
23
98
97
78
18
93
92
73
n/a
13
88
87
68
8
83
82
63
3
78
77
58
73
72
53
n/a
68
67
48
3" Pipe
Capacity
110
135
45
70
90
38
113
112
93
33
108
107
88
28
103
102
83
23
98
97
78
18
93
92
73
n/a
13
88
87
68
8
83
82
63
3
78
77
58
73
72
53
n/a
68
67
48
110
135
93
89
88
84
83
79
78
74
73
69
68
64
63
59
58
54
53
49
48
44
110
135
93
89
88
84
83
79
78
74
73
69
68
64
63
59
58
54
53
49
48
44
Page 21 of 58