Model Specifications - Eaton 9PX1000IRTANZ-L User Manual

Table of Contents

Advertisement

Model Specifications

Table 10. Electrical Input
Model
9PX1000IRTANZ-L
9PX1500IRTANZ-L
9PX2000IRTAU-L
9PX3000IRTANZ-L
Table 11. Electrical Input Connections
Model
9PX1000IRTANZ-L
9PX1500IRTANZ-L
9PX2000IRTAU-L
9PX3000IRTANZ-L
Table 12. Electrical Output
All Models
Voltage Regulation
Efficiency
Frequency Regulation
Nominal Output
Frequency
Output Overload
44
Eaton 9PX Lithium-Ion
Default Input
(Voltage/Max Current)
240V / 6A
240V / 9A
240V / 10A
240V / 16A
Nominal Frequency
Frequency Range
Bypass Voltage Range
Noise Filtering
Input Connection
IEC-C14
IEC-C20
Normal Mode
±1%
98% (High Efficiency mode)
94% for 3K, 93% for 2K
Sync with line ±5% of nominal line
frequency (outside this range: ±0.5% of
auto-selected nominal frequency)
[200V] [208V] [220V] [230V] [240V] (Voltage configurable)
50 or 60 Hz, autosensing or configurable as a frequency converter
Online mode:
102%~130% :12s
130%~150% :2s
>150% :shutdown after 300ms
Percent is based on nominal Watt/VA.
Transfer behavior can change (see output mode setting)
Battery mode:
102%~130% :12s
>130% :2s
>150% : shutdown after 300 ms
:
P-164001006—Rev 01
Input Nominal Voltages
Input Voltage Window at Rated
Load
200V–240V
50/60Hz auto-sensing
40-70Hz before transfer to battery
-20% / +15% of nominal value (default)
Input EMC filter
Input cable
IEC10A
IEC16A
Battery Mode
±2%
89% for 3K
90% for 2K
±0.5% of auto-selected nominal
frequency
at 100%load:176V-276V
at <33% load: 100-276V

Advertisement

Table of Contents
loading