6.3 Battery Settings Reset - Eaton 9PX1000IRTANZ-L User Manual

Table of Contents

Advertisement

1.
Unplug the EBM power cable and battery detection cable from the UPS. If additional EBM(s) are installed,
unplug the EBM power cable and battery detection cable from each EBM.
2.
Replace the EBM(s). See "Recycling the used equipment" for proper disposal.
A small amount of arcing may occur when connecting an EBM to the UPS. This is normal and will not harm
personnel. Insert the EBM cable into the UPS battery connector quickly and firmly.
3.
Plug the EBM cable(s) into the battery connector(s). Up to four EBMs may be connected to the UPS.
4.
Verify that the EBM connections are tight and that adequate bend radius and strain relief exist for each
cable.
5.
Connect the battery detection cable(s) to the connector of the UPS and of the EBM(s).
6.
Continue to the
6 6 . . 3 3
B B a a t t t t e e r r y y S S e e t t t t i i n n g g s s R R e e s s e e t t
After replacement of the internal UPS batteries and extended battery modules and before powering the UPS to
the online mode the BMS auto setup and battery life settings will need to be reset in the "Control" menu of the
display.
1.
Reset the BMS auto setup function in the "Functions Reset" option of the control menu.
Figure 11. BMS Auto Setup Reset
Online mode
100 %
2.4kW
19min
3.0kVA
Efficiency: 94%
Press the Enter Button
to advance the menu
2.
Reset the battery life counter in the "Functions Reset" option of the control menu.

6.3 Battery Settings Reset

Menu
Measurements
Control
100 %
Settings
Event log
1 EBM
Fault log
Identification
Register product
Control
Go to bypass
Load segments
UPS firmware
Connectivity test
Functions reset
section before restarting the unit.
Functions reset
UPS firmware
Reset Fault state
Reset power usage
BMS auto setup
Reset battery life
NMC card reset
Eaton 9PX Lithium-Ion
P-164001006—Rev 01
Battery Settings Reset
BMS auto setup
Are you sure?
Yes
No
BMS auto setup
Done
35