Silencing The Alarm - Eaton 9PX1000IRTANZ-L User Manual

Table of Contents

Advertisement

Silencing the Alarm

Conditions
The UPS does not provide the expected
backup time.
Bypass mode
LED is on.
Power Overload
LED is on.
UPS Overtemperature
LED is on.
1 beep every 3 seconds
The UPS does not start
7 7 . . 2 2
S S i i l l e e n n c c i i n n g g t t h h e e A A l l a a r r m m
Press the ESC (Escape) button on the front panel display to silence the alarm. Check the alarm condition and
perform the applicable action to resolve the condition. If the alarm status changes, the alarm beeps again,
overriding the previous alarm silencing.
7 7 . . 3 3
S S e e r r v v i i c c e e a a n n d d S S u u p p p p o o r r t t
If you have any questions or problems with the UPS, call your Local Distributor or your local service
representative and ask for a UPS technical representative. Please have the following information ready when
you call for service:
Model number
Serial number
Firmware version number
Date of failure or problem
Symptoms of failure or problem
Customer return address and contact information
40
Eaton 9PX Lithium-Ion
Possible cause
The batteries need charging or service.
An overload or a fault has occurred, or a
command has been received and the UPS
is in Bypass
Power requirements exceed the UPS
capacity (greater than 100% of nominal;
see "User Settings" on page 8 for
specific output overload ranges).
The UPS internal temperature is too high
or a fan has failed. At the warning level,
the UPS generates the alarm but remains
in the current operating state. If the
temperature rises another 10°C, the UPS
transfers to Bypass mode or shuts down
if Bypass is unusable.
The input source is not connected
correctly.
The Remote Power Off (RPO) switch is
active or the RPO connector is missing.
P-164001006—Rev 01
Action
Apply utility power for 48 hours to charge
the batteries. If the condition persists,
contact your service representative.
Equipment is powered but not protected
by the UPS. Check for one of the
following alarms: overtemperature,
overload or UPS LED is on. failure.
Remove some of the equipment from the
UPS. The UPS continues to operate, but
may switch to Bypass mode or shut down
if the load increases. The alarm resets
when the condition becomes inactive.
If the UPS transferred to Bypass mode,
the UPS will return to normal operation
when the temperature drops 5°C below
the warning level. If the condition
persists, shut down the UPS.
Clear vents and remove any heat sources.
Allow the UPS to cool. Ensure the airflow
around the UPS is not restricted. Restart
the UPS. If the condition continues to
persist, contact your service
representative.
Check the input connections.
If the UPS Status menu displays the
"Remote Power Off" notice, inactivate the
RPO input.

Advertisement

Table of Contents
loading

Table of Contents