Mitsubishi Electric FR-E720-0.4K Instruction Manual page 33

Hide thumbs Also See for FR-E720-0.4K:
Table of Contents

Advertisement

Acquiring large starting torque and low speed torque (Advanced magnetic flux vector control, General-purpose magnetic flux vector control) (Pr. 71, Pr. 80, Pr. 81, Pr. 800)
5.3.1
Selection method of Advanced magnetic flux vector control
Motor
Mitsubishi Electric
SF-JR
standard motor
SF-HR
Mitsubishi Electric high
Others
efficiency motor
SF-JRCA 4P
Mitsubishi Electric
SF-HRCA
constant-torque motor
Others (SF-JRC, etc.)
Other manufacturer's
standard motor
Other manufacturer's
constant-torque motor

Refer to Chapter 4 of the Instruction Manual (Applied) for other settings of Pr. 71 and offline auto tuning.
Set the motor overheat protection. (Pr. 9) (Refer to page 32.)
Set the motor capacity and the number of motor poles.
(Pr. 80, Pr. 81) (Refer to page 28.)
Set the rated motor voltage and frequency.
(Pr. 83, Pr. 84) (Refer to page 28.)
Select the control method. (Pr. 800) (Refer to page 28.)
Set the operation command. (Refer to page 20.)
As required
 Perform offline auto tuning. (Pr. 96) (
NOTE
 Uneven rotation slightly increases as compared to the V/F control. (It is not suitable for machines such as grinding
machine and wrapping machine which requires less uneven rotation at low speed.)
 When a surge voltage suppression filter (FR-ASF-H/FR-BMF-H) is connected between the inverter and motor, output
torque may decrease.
REMARKS
 Use Pr. 89 to adjust the motor speed fluctuation at load fluctuation.
Perform secure wiring.
(Refer to page 8.)
Set the motor. (Pr. 71)
Set the rated motor current (A) in Pr.9 Electronic thermal O/L relay.
Set motor capacity (kW) in Pr. 80 Motor capacity and
the number of motor poles (number of poles) in Pr. 81 Number of motor poles.
(V/F control is performed when the setting is "9999" (initial value).
Set the rated motor voltage (V) in Pr.83 Rated motor voltage, and
set the rated motor frequency (Hz) in Pr.84 Rated motor frequency.
Set "20" (initial value) in Pr. 800 to make Advanced magnetic flux vector control
valid.
Select the start command and speed command.
(1) Start command
1) Operation panel: Setting by pressing
2) External command: Setting by forward rotation or reverse rotation command
(terminal STF or STR)
(2) Speed command
1) Operation panel: Setting by pressing
2) External analog command: Set by the terminal 2 or the terminal 4
3) Multi-speed command: Set by the external signals (RH, RM, RL)
Test run
Refer to Chapter 4 of the Instruction Manual (Applied).)
Pr. 71 Setting 
0 (initial value)
40
3
Offline auto tuning is necessary.
1
50
13
Offline auto tuning is necessary.
3
Offline auto tuning is necessary.
13
Offline auto tuning is necessary.
(
Refer to Chapter 4 of the Instruction Manual (Applied).)
Remarks




of the operation panel
of the operation panel
29
5

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents