Mitsubishi Electric FR-E720-0.4K Instruction Manual page 26

Hide thumbs Also See for FR-E720-0.4K:
Table of Contents

Advertisement

Start/stop from the operation panel (PU operation)
5.1.3
Setting the frequency by switches (three-speed setting) (Pr. 4 to Pr. 6)
POINT
 Use the operation panel (
 Switch ON the RH, RM, or RL signal to give a frequency command.
 Set "4" (External/PU combined operation mode 2) in Pr. 79 Operation mode selection.
[Connection diagram]
High speed
Middle speed
Low speed
Operation example
Operation at low speed (10Hz)
Screen at power-ON
1.
The monitor display appears.
Easy operation mode setting
2.
Press
and
Operation mode selection
3.
Turn
until "
Operation mode setting
4.
Press
to enter the setting. (Set "4" in Pr.79.)
"
" and "
Start
5.
Turn ON the low-speed switch (RL).
Acceleration  constant speed
Press
to start running.
6.
The frequency value on the indication increases in Pr. 7 Acceleration time, and "
[RUN] indicator is lit during forward rotation operation and blinks slowly during reverse rotation operation.
Deceleration
Press
to stop.
7.
The frequency value on the indication decreases in Pr. 8 Deceleration time, and the motor stops rotating with "
displayed.
Stop
8.
Turn OFF the low-speed switch (RL).
REMARKS
 The initial values of the terminals RH, RM, RL are 60Hz, 30Hz, and 10Hz. (Use Pr. 4, Pr. 5 and Pr. 6 to change.)
 In the initial setting, when two or three of multi-speed settings are simultaneously selected, priority is given to the set frequency
of the lower signal.
For example, when the RH and RM signals turn ON, the RM signal (Pr. 5) has a higher priority.
 Maximum of 15-speed operation can be performed. (
22
)
to give a start command.
Inverter
RH
RM
RL
SD
for 0.5s. "
" appears, and the [PRM] indicator blinks.
" appears. [PU] and [PRM] indicators blink.
" appear alternately. [PU] and [EXT] indicators are lit.
Operation
panel
RH
RM
RL
Operation
Refer to Chapter 4 of the Instruction Manual (Applied).)
Speed 1
(High speed)
Speed 2
(Middle speed)
Speed 3
(Low speed)
Time
ON
ON
ON
" (10.00Hz) appears.
" (0.00Hz)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents