2.2
Installation of the inverter and instructions
(1) Installation of the inverter
Enclosure surface mounting
Remove the front cover and wiring cover to fix the inverter to the surface. (Remove the covers in the directions of the arrows.)
FR-E720-0.1K to 0.75K
FR-E720S-0.1K to 0.4K
FR-E710W-0.1K to 0.4K
Front cover
Note
 When encasing multiple inverters, install them in parallel as a cooling
measure.
 Install the inverter vertically.
 For heat dissipation and maintenance, take at least the clearances
shown in the table below from the inverter to the other devices and to
the enclosure surface.
5cm
5cm
Measurement
position
-10 C to +50 C
(non-freezing)

Take 5cm or more clearances for 5.5K or higher.

When using the inverters at the surrounding air temperature of 40C or less, the inverters can be installed without any clearance between
them (0cm clearance).
(2) Environment
Before installation, check that the environment meets the specifications on page 45.
Note
 Install the inverter on a strong surface securely and vertically with bolts.
 Leave enough clearances and take cooling measures.
 Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
 Install the inverter on a nonflammable wall surface.
 When designing or building an enclosure for the inverter, carefully consider influencing factors such as heat
generation of the contained devices and the operating environment.
FR-E720-1.5K to 3.7K
FR-E740-0.4K to 7.5K
FR-E720S-0.75K or higher
FR-E710W-0.75K
Front cover
Wiring cover
Measurement
10cm or more
position
5cm
1cm or
1cm or
∗1, ∗2
∗1, ∗2
more
more
10cm or more
Installation of the inverter and instructions
Front cover 1
Wiring cover
1cm or
∗1
more
FR-E720-5.5K to 15K
FR-E740-11K, 15K
Wiring cover
2
7