Toshiba MMU-UP0071YHP-UL Service Manual page 47

Table of Contents

Advertisement

[Control items]
Function
Manual prohibition release
Card Input 1
(Manual operation)
Manual prohibition release
Card Input 2
(Automatic operation)
Operation status continues
(Do nothing)
Card Input 3
Manual prohibition release
(The status returns to operating condition before
Card Input 4
removing the card.)
1) To change a setting temperature by changing data at
DN code No. 172 to 174.
2) The operation mode can be set by changing data
(0000, 0001, 0002) at DN code No. 16b.
0000: operation mode is the same at the current mode.
(factory setting default)
0001: operation mode returns to the previous mode when
card was inserted. (in case of the previous mode is
Card Input 5
off operation, the operation mode is also off.)
0002: operation mode starts at the same previous mode
when the card was inserted. (the operation mode
is on operation even the previous mode is off
operation.)
See contents below for DN settings and detailed
operations.
* For the card switch box that does not involve contact operation described above, convert signals with a relay including a
normally-closed contact.
[Card input setup.5 Code (DN)]
DN
Item
16C Open mode Set temp. (Cool, Dry)
16d Open mode Set temp. (Heat)
16E Open mode Set temp. (Auto)
16F Open mode Fan speed (All operation mode)
170 Open mode Wind direction (Cool, Dry, Fan)
171 Open mode Wind direction (Heat)
16A Open mode Operation
172 Close mode Set temp. (Cool, Dry)
173 Close mode Set temp. (Heat)
174 Close mode Set temp. (Heat)
16b Close mode Operation
Close (Status that card is inserted)
-0015 5ºF(-15ºC) to
-0015 : 5ºF(-15ºC) to
-0015 : 5ºF(-15ºC) to
0000 No change
0000 No change
0000 No change
0004 F4
0000 No change
-0015 5ºF(-15ºC)
-0015 5ºF(-15ºC)
-0015 5ºF(-15ºC)
0000 No change
0001 Card ON mode operation
0002 Run operation (Card ON mode setting)
External contact terminal
Open (Status that card is taken out)
Manual prohibition
(Operation stop)
Manual prohibition
(Operation stop)
Operation status continues and setting temperature
changes
(COOL/DRY: 84.2ºF(29ºC), HEAT: 64.4ºF(18ºC))
Manual prohibition
(Operation stop)
1) To change a setting temperature, fan speed and wind
direction by changing data at DN code No. 16C to 171.
2) The operation mode can be set by changing data
(0000, 0001) at DN code No. 16A.
0000: operation mode is the same at the current mode.
(factory setting default)
0001: operation automatically starts.
See contents below for DN settings and detailed
operations.
Description
0060 140ºF(60ºC)
0060 140ºF(60ºC)
0060 140ºF(60ºC)
0001 HH
0002 H
0001 F1
0002 F2
0001 F1
0002 F2
0005 F5
0001 Run operation
0060 140ºF(60ºC)
to
0060 140ºF(60ºC)
to
0060 140ºF(60ºC)
to
- 47 -
At shipment
0027 80.6ºF(27ºC)
0020 68ºF(20ºC)
0024 75.2ºF(24ºC)
0003 L
0000 No change
0003 F3
0000 No change
0003 F3
0000 No change
0000 No change
0024 75.2ºF(24ºC)
0024 75.2ºF(24ºC)
0024 75.2ºF(24ºC)