Basic Settings - Omron CS Series Operation Manual

Ethernet units construction of networks
Hide thumbs Also See for CS Series:
Table of Contents

Advertisement

Basic Settings

2-8

Basic Settings

46
6. Make the required settings (i.e., the IP address in this example).
7. After entering the correct values, click the Set Button followed by the Reg-
ist Button to register them.
The Set Button is used to transfer the entered values from the personal com-
puter, and temporarily register them in the Ethernet Unit.
The Regist Button stores the set values that have been temporarily registered
in the Ethernet to the flash memory (non-volatile memory) of the CPU Unit.
The Ethernet Unit reads the unit settings from flash memory (non-volatile
memory) when the power is turned ON or the Unit is restarted. Therefore,
when making the unit settings using the Web function, always click the Set
Button before the Regist Button. Otherwise the entered set values will not be
used. The Set Button and Regist Button are provided on the window for each
setting item.
The functions of the other buttons are as follows:
• Cancel Button
Use this button to cancel the entered value and display the value that was
previously set with the Set Button again. If the Set Button has not been
clicked, the value that was read from the CPU Unit's flash memory (non-
volatile memory) when the Ethernet Unit was started will be displayed.
• Reload Button
Use this button read and display the values saved in the CPU Unit's flash
memory (non-volatile memory).
8. To enable the unit settings that have been registered in the CPU Unit's
flash memory (non-volatile memory, turn the power to the PLC OFF and
ON again, or restart the Ethernet Unit.
The following items comprise the basic settings in the Ethernet Unit
(100Base-TX) setup. Each item is described in detail below.
• IP address
• Subnet mask
• Broadcast settings
• Baud rate
• TCP/IP keep-alive
• IP router table
■ IP Address
For the IP address, set the Ethernet Unit's local IP address.
Section 2-8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cj seriesCj1w-etn21

Table of Contents