Powering Up The Indoor Unit; Setting The Pump Speed; Field Settings - Daikin EKHBX008BA Series Installation Manual

Indoor unit for air to water heat pump system
Hide thumbs Also See for EKHBX008BA Series:
Table of Contents

Advertisement

6
Internal wiring
Visually check the switch box on loose connections or damaged
electrical components.
7
Fixation
Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.
8
Damaged equipment
Check the inside of the unit on damaged components or
squeezed pipes.
9
Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, call your local dealer.
10 Power supply voltage
Check the power supply voltage on the local supply panel. The
voltage must correspond to the voltage on the identification label
of the unit.
11 Air purge valve
Make sure the air purge valve is open (at least 2 turns).
12 Pressure relief valve
Check if the backup heater is completely filled with water by
operating the pressure relief valve. It should purge water instead
of air.
Operating the system with the backup heater not
NOTE
completely filled with water will damage the backup
heater!
13 Shut-off valves
Make sure that the shut-off valves are correctly installed and
fully open.
NOTE
Operating the system with closed valves will damage
the pump!

Powering up the indoor unit

When power supply to the indoor unit is turned on, "88" is displayed
on the user interface during its initialisation, which might take up to
30 seconds. During this process the user interface cannot be
operated.

Setting the pump speed

The pump speed can be selected on the pump (see
components" on page
10).
The default setting is high speed (III). If the water flow in the system
is too high (e.g., noise of running water in the installation) the speed
can be set to medium speed (II) or low speed (I).
The available external static pressure (ESP, expressed in kPa) in
function of the water flow (l/min) is shown in the graph below.
70
60
50
40
30
II
20
I
10
0
12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42
EKHBH/X008BA
Indoor unit for air to water heat pump system
4PW54185-1B
III
[ l/min ]

Field settings

The indoor unit shall be configured by the installer to match the
installation environment (outdoor climate, installed options, etc.) and
user demand. Thereto, a number of so called field settings are
available. These field settings are accessible and programmable
through the user interface on the indoor unit.
Each field setting is assigned a 3-digit number or code, for example
[1-03], which is indicated on the user interface display. The first digit
[1] indicates the 'first code' or field setting group. The second and
third digit [03] together indicate the 'second code'.
A list of all field settings and default values is given under
settings table" on page
columns to register the date and value of altered field settings at
variance with the default value.
A detailed description of each field setting is given under
description" on page
Procedure
To change one or more field settings, proceed as follows.
3
2
Press the z button for a minimum of 5 seconds to enter FIELD
1
SET MODE.
The $ icon (3) will be displayed. The current selected field
setting code is indicated ; (2), with the set value displayed to
the right - (1).
Press the bgi button to select the appropriate field
2
setting first code.
Press the bgj button to select the appropriate field
3
"Main
setting second code.
4
Press the pfi button and pfj button to change
the set value of the select field setting.
5
Save the new value by pressing the pr button.
6
Repeat step 2 through 4 to change other field settings as
required.
7
When finished, press the z button to exit FIELD SET MODE.
Changes made to a specific field setting are only
NOTE
stored when the pr button is pressed. Navigating to a
new field setting code or pressing the z button will
discard the change made.
Before shipping, the set values have been set as
shown under
When exiting FIELD SET MODE, "88" may be
displayed on the user interface LCD while the unit
initialises itself.
32. In this same list, we provided for 2
24.
"Field settings table" on page
"Field
"Detailed
1
32.
Installation manual