▪ Install freeze protection valves (optional – field supply) at all
lowest points of the field piping.
▪ Normally closed valves (recommended – field supply) can prevent
that all water from indoor piping is drained when the freeze
protection valves open.
NOTICE
When freeze protection valves are installed, set the
minimum cooling setpoint (default=7°C) at least 2°C higher
than the maximum opening temperature of the freeze
protection valve. If lower, freeze protection valves can
open during cooling operation.
For more information, see the installer reference guide.
5.2.4

To fill the domestic hot water tank

See the installation manual of the domestic hot water tank.
5.2.5

To insulate the water piping

The piping in the complete water circuit MUST be insulated to
prevent condensation during cooling operation and reduction of the
heating and cooling capacity.
Outdoor water piping insulation
NOTICE
Outside piping. Make sure the outside piping is insulated
as instructed to protect against hazards.
For piping in free air, it is recommended to use the insulation
thickness as shown in below table as a minimum (with λ=0.039  W/
mK).
Piping length (m)
<20
20~30
30~40
40~50
For other cases the minimum insulation thickness can be determined
using the Hydronic Piping Calculation tool.
The Hydronic Piping Calculation tool is part of the Heating Solutions
Navigator
which
can
professional.standbyme.daikin.eu.
Please contact your dealer if you have no access to Heating
Solutions Navigator.
This recommendation ensures good operation of the unit, however,
local regulations may differ and shall be followed.
6

Electrical installation

DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
Do NOT push or place redundant cable length in the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
EBLA04~08E2V3+E23V3 + EDLA04~08E2V3+E23V3
Daikin Altherma 3 M
4P685229-1D – 2022.10
Minimum insulation thickness
(mm)
19
32
40
50
be
reached
via
https://
6.1

About electrical compliance

Equipment
complying
with
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Item
X1M
X2M
X3M
X4M
X5M
X7M
X9M
X10M
6.3

Connections to the outdoor unit

Item
Power supply (main)
See
"6.3.2 To connect the main power
supply" [ 4  17].
Power supply (backup
See
"6.3.3 To connect the backup heater
supply" [ 4  19].
heater)
power
(in case of outdoor unit
with integrated backup
heater)
Backup heater kit +
See
"6.3.4 External backup heater
kit" [ 4  20].
Bypass valve kit
(in case of external
backup heater kit)
User interface
See
"6.3.5 To connect the user
interface" [ 4  22].
Shut-off valve
See
"6.3.6 To connect the shut-off
valve" [ 4  24].
Electricity meters
See
"6.3.7 To connect the electricity
meters" [ 4  25].
Domestic hot water
See
"6.3.8 To connect the domestic hot
pump" [ 4  25].
pump
water
Alarm output
See
"6.3.9 To connect the alarm
output" [ 4  25].
Space cooling/heating
See
"6.3.10 To connect the space cooling/
operation control
heating ON/OFF
Changeover to
See
"6.3.11 To connect the changeover to
external heat source
external heat
control
Power consumption
See
"6.3.12 To connect the power
digital inputs
consumption digital
Safety thermostat
See
"6.3.13 To connect the safety
thermostat (normally closed
contact)" [ 4  27].
Smart Grid
See
"6.3.14 To connect a Smart
Grid" [ 4  27].
6 Electrical installation
EN/IEC  61000‑3‑12
(European/
Tightening torque (N•m)
2.45 ±10%
0.88 ±10%
0.88 ±10%
2.45 ±10%
0.88 ±10%
0.88 ±10%
2.45 ±10%
0.88 ±10%
Description
output" [ 4  26].
source" [ 4  26].
inputs" [ 4  27].
Installation manual