MAINTENANCE

SHUTDOWNS

If out of service more than one week, flush mixing
chamber.
Turn pump off.
Place unit power switch in On position to establish
water flow for five minutes.
If out of service for more than two weeks, flush pump
and mixing chamber.
Connect pump suction to a container of mineral oil
(not water).
Place unit power switch in On position to establish
water flow.
Turn pump on and run for three minutes.
Turn pump off.
Continue water flow for five additional minutes.
Drain water from chamber and piping to prevent
freezing.
MAINTENANCE
1. Clean ancillary water and/or polymer strainers
weekly.
2. Flush
system
monthly
procedure.
3.
Refer to the appendix for specific information on
drawings, part identification, and components.

SPECIAL TOOLS

No special tools needed for operation, maintenance, and
repair of components.

LUBRICATION

No lubrication is required.

PREDICTED LIFE SPAN

There is no predicted life span of wear parts as each
application and operation varies.
following
one
week

OPERATING PROCEDURES

For normal operation, once settings are adjusted based
on operation parameters, the system can simply be
turned ON or OFF. Special operating instructions for
Seasonal operation do not apply.
EMERGENCY OPERATING INSTRUCTIONS
Emergency operating instructions do not apply to
Siemens Water Technologies – Stranco Products
equipment. In case of an emergency, TURN OFF
POWER TO STOP RUNNING.
DISASSEMBLY, REPAIR, & REASSEMBLY
This equipment is an open-frame design. It allows for
easy removal of all components. There are no special
procedures for removal of parts. If assistance is
required, contact Siemens Water Technologies –
Stranco Products Technical Service at 800-882-6466.

RECOMMENDED SPARE PARTS

QTY. PART #
1
SP-155PBX
1
7802910
1
1450318
1
1414001
1
1410002
1
28391-1

PUMP REPLACEMENT

QTY.
PART #
1
AA771-155PBX
TO ORDER PARTS
You may order parts by calling, faxing or mailing your
order.
Phone 800.882.6466 and ask for PolyBlend Parts.
Hours: 8 a.m. - 5 p.m., Central Time, M - F.
Fax
Our fax number is 815.932.5634.
E-mail
Our E-mail address is stranco@usfilter.com
Address Siemens Water Technologies Corp.
P.O. Box 389
595 Industrial Drive
Bradley, IL 60915
-3-
DESCRIPTION
Pump Liquid End
Chamber Mechanical Seal
Belt, Chamber
Bearing, Chamber Base
Bearing, Chamber Top
Pump Head
DESCRIPTION
Pump