Daikin VRV IV+ RYYQ8U7Y1B Series Installer And User Manual page 157

Hide thumbs Also See for VRV IV+ RYYQ8U7Y1B Series:
Table of Contents

Advertisement

Main code
Master
RYYQ+RYMQ+RXYQ
VRV IV+ heat pump
4P546228-1C – 2021.11
Sub code
Slave 1
Slave 2
Cause
Discharge temperature sensor
malfunction (R21T): open
circuit - A1P (X19A)
Discharge temperature sensor
malfunction (R21T): short
circuit - A1P (X19A)
Discharge temperature sensor
malfunction (R22T): open
circuit - A1P (X19A)
Discharge temperature sensor
malfunction (R22T): short
circuit - A1P (X19A)
Compressor casing
temperature sensor
malfunction (R8T): open
circuit - A1P (X19A)
Compressor casing
temperature sensor
malfunction (R8T): short
circuit - A1P (X19A)
Compressor casing
temperature sensor
malfunction (R9T): open
circuit - A1P (X19A)
Compressor casing
temperature sensor
malfunction (R9T): short
circuit - A1P (X19A)
Suction temperature sensor
malfunction (R3T) - A1P
(X30A)
De-icing temperature sensor
malfunction (R7T) - A1P
(X30A)
Liquid temperature sensor
(after subcool HE) malfunction
(R5T) - A1P (X30A)
Liquid temperature sensor
(coil) malfunction (R4T) - A1P
(X30A)
Gas temperature sensor (after
subcool HE) malfunction (R6T)
- A1P (X30A)
23
Troubleshooting
|
Solution
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Installer and user reference guide
157

Hide quick links:

Advertisement

Table of Contents
loading