Mounting
4.1 Safety notices for installation
When used in hazardous environments corresponding to Class I, Division 2 or Class I,
Zone 2, the device must be installed in a cabinet or a suitable enclosure.
Safety notices for use according to ATEX and IECEx
If you use the device under ATEX or IECEx conditions you must also keep to the following
safety notices in addition to the general safety notices for protection against explosion:
To comply with EC Directive 2014/34/EU (ATEX 114) or the conditions of IECEx, this
enclosure or cabinet must meet the requirements of at least IP54 in compliance with EN
60529.
If the cable or conduit entry point exceeds 70 °C or the branching point of conductors
exceeds 80 °C, special precautions must be taken. If the equipment is operated in an air
ambient in excess of 60 ℃, only use cables with admitted maximum operating temperature
of at least 80 ℃.
Safety notices when using according to FM
If you use the device under FM conditions you must also keep to the following safety notices
in addition to the general safety notices for protection against explosion:
EXPLOSION HAZARD
For operation the device is intended to be installed within an enclosure/control cabinet. The
inner temperature of the enclosure/control cabinet corresponds to the ambient temperature
of the device. Use installation wiring connections with admitted maximum operating
temperature of at least 30 °C higher than maximum ambient temperature.
40
WARNING
WARNING
WARNING
WARNING
Operating Instructions, 04/2018, C79000-G8976-C442-04