Figure 65. On/Off Settings Menu - Eaton 9PXM8S4K User Manual

Table of Contents

Advertisement

O O n n / / O O f f f f S S e e t t t t i i n n g g s s
The On/Off Settings Menu enables/disables selected automatic restart and shutdown functions.

Figure 65. On/Off Settings Menu

Settings
Local Settings
In/Out settings
On/Off settings
Battery settings
Input signals
Comm settings
User password enable
User password settings
Select On/O Settings
On/Off settings
Forced Reboot
Auto Restart
Site wiring fault
Energy saving
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10
Display Menu Screens
[Enabled] [Disabled]
[Timer] [10s] ... [180s]
Forced reboot
When mains recover during
a shutdown sequence:
If set to Enabled, shutdown
Disabled
sequence will complete and
Enabled
wait 10 seconds prior to restart,
If set to Disabled, shutdown
sequence will not complete,
UPS stays on.
Default Value: [Enabled]
Auto restart
Disabled
[Enabled] [Disabled]
Enabled
Site Wiring Fault
[Enabled] [Disabled]
Prevents from starting
Disabled
the UPS in case of phase
Enabled
vs neutral wires swapping.
Default: Disabled
Energy saving
[Shut o level] [Disabled]
(Shut off level)
[Timer] [1min] ... [15min]
Disabled
[Level] [200W] ... [2000W]
200 W
If Enabled, UPS will shut-down
400 W
after de ned duration. of
back-up time, if load is less
600 W
than set value
1000 W
Default: Disabled [200W]
1500 W
2000 W
79