Rack-Mount Installation

1.
Select the location for the brackets at the floor intersection beside the intended cabinet location.
2.
Attach the brackets to the cabinet base as shown in
3.
Roll the UPS cabinet to its intended location. Position the rear section of the cabinet base under the open
ends of the stabilizer brackets as far as the cabinet will go.
4.
Turn all four leveling feet counter-clockwise until the cabinet is level.
5.
Using the proper type of customer-supplied screws for the intended mounting surface, attach each
bracket as shown in
Figure 9. Floor Anchor Bracket Installation
Spacer
2 2 . . 6 6
R R a a c c k k - - M M o o u u n n t t I I n n s s t t a a l l l l a a t t i i o o n n
The 12-slot UPS weighs 93 kg (204 lb) with the caster cart. Install the cabinet in the rack before installing power
and battery modules and before making connections to the intended power source.
The Eaton 9PXM UPS and the battery cabinet are very heavy with power modules and two battery modules per
slot installed. If installed, before moving the cabinets, remove the power modules and battery two battery
modules per slot (see
12
4–20kVA Users Guide P-164000669 4–20kVA Users Guide P-164000669—Rev 10
Figure 9
. All screws must be properly driven into the structural material.
Mount Bolts
Floor Bolt
Slots
"9.1 Routine Maintenance
Figure 9
.
Leveling
Foot
Floor Anchor
*Installation to be updated
Bracket
(spacers/bolts)
" ).