5
|
Technical data
All/individual control
Service manual
98
draft – 07/02/2022 15:12
Up to 64 units, a combination of air conditioners and VAM units, can be
connected to the F1 and F2 terminals.
This system does NOT require group number setting for central control (auto-
address system). The central control group number is automatically assigned if
the adapter PCB (KRP2A51) or schedule timer (DST301B51) is connected.
The adapter PCB and the schedule timer CANNOT be used together. The adapter
PCB allows on/off control. The schedule timer allows on/off control with a weekly
schedule.
The adapter PCB can be connected to the electric component mounting base of
either the VAM unit or the air conditioner.
d
1
F1 F2
F1 F2
c
F1 F2
VAM 1
F1 F2
VAM 2
F1 F2
P1
P2
VRV 1
F1 F2
P1
P2
b
a Controller for air conditioner
b Maximum length of connection line: 1000 m
c Schedule timer
d ON/OFF controller
VAM 1 VAM heat reclaim ventilation unit 1
VAM 2 VAM heat reclaim ventilation unit 2
VRV 1 VRV indoor unit 1
If the ON/OFF controller (DCS301B51) is used, the following is valid:
Up to 64 units, a combination of air conditioners and VAM units, can be
connected to the F1 and F2 terminals.
Up to 4 ON/OFF controllers can be connected.
A central control group number must be assigned to each VAM unit and air
conditioner. See "The central control group number setting" in the operation
manual of the ON/OFF controller for information about setting the group
number.
Use the air conditioner's controller to configure the initial settings.
2
3
4
F1 F2
F1 F2
P1 P2
a
P1 P2
a
VAM350~2000J8VEB + EKVDX32~100A2VEB
VRV system air conditioner
ESIE22-07 – 2022.02