Daikin VAM350J8VEB Service Manual page 96

Vrv system air conditioner
Hide thumbs Also See for VAM350J8VEB:
Table of Contents

Advertisement

5
|
Technical data
Direct duct connection
Central control system
Service manual
96
draft – 07/02/2022 15:12
Activate setting 17-8-02 to set the central zone link to ON. No further settings are
required.
NOTICE
Direct duct connection is NOT allowed with EKVDX indoor units.
The line connections are the same as for the 1-group linked-control system.
VRV
P1
P2
a
a Controller for air conditioner
b Controller for air conditioner
c Maximum length of connection line: 500 m
VRV VRV indoor unit
VAM VAM heat reclaim ventilation unit
Initial settings
Activate below setting for direct duct connection. This direct duct configuration
ONLY works if P1/P2 is connected.
Mode number: 17
Switch number: 5
Position number: 07
Other functions
Like in a 1-group linked-control system, other VAM functions can also be
configured.
To change the settings, P1/P2 of the controller MUST be connected to the heat
reclaim ventilation units. The controller can be removed after the settings are
changed.
If the unit is supposed to operate without controller, do NOT switch it on with the
controller connected. Otherwise, the unit will give an error once the controller is
removed, because it will keep on searching for the controller signal. To resolve the
error, perform a power reset without the controller connected.
VAM
P1 P2
c
P1 P2
P1P2
b
VAM350~2000J8VEB + EKVDX32~100A2VEB
VRV system air conditioner
ESIE22-07 – 2022.02