Trane Axiom GEH Series Installation, Operation And Maintenance Manual page 61

Water source heat pump
Table of Contents

Advertisement

piping will prevent condensation from forming on the
pipe and dripping on the floor.
Notes:
Trane does not provide insulation on the
economizing piping package. The insulation
must be field provided and field installed.
Trane does not provide condensate
overflow protection of the waterside
economizer. This must be field provided
and installed.
8. Field pipe the drain lines of the waterside economizer
and water-source heat pump. Both the WSE and unit
condensate drains must be separately trapped for
proper handling of condensation (see
). Both Vertical and Horizontal units will be piped similar
to each other. The drain connection is located on the
bottom side of the economizing coil.
Figure 69. Step 8
H
L
J
H
J
Table 44. Economizer part numbers
Supply-Air
Arrangement
GEVG006-012
GEVG015-018
Left Supply
GEVG024-030
GEVG036-042
GEVG048-060
GEVG006-012
GEVG015-018
Right Supply
GEVG024-030
GEVG036-042
GEVG048-060
WSHP-SVX01AC-EN
Figure 69, p. 61
NEGATIVE PRESSURE TRAPPING
H=1" (25.4 mm) FOR EVERY 1"
(25.4 mm) OF MAXIMUM
NEGATIVE STATIC PRESSURE
L
+1" (25.4 mm).
J= HALF OF H.
L=H+J+ PIPE DIAMETER +INSULATION.
Unit
Part Number
WSHPECN00015
WSHPECN00016
WSHPECN00017
WSHPECN00018
WSHPECN00019
WSHPECN00022
WSHPECN00023
WSHPECN00024
WSHPECN00025
WSHPECN00026
Waterside Economizer Installation for
Vertical 0.5 to 5 Ton Units
The following steps were sequenced to aid in the
installation and pairing of a water side economizer to a 0.5
to 5 ton vertical water source heat pump.
1. Remove the filter bracket from the unit. It is secured by
five screws: three on top (circled) and two on the
bottom (not shown). Do not discard the filter brackets.
Figure 70. Step 1
2. Mount the waterside economizer to the unit. It is
secured to the unit using the five engagement holes
that were used for the filter brackets: three on top and
two on the bottom.
Figure 71. Step 2
3. Attach the filter brackets to the waterside economizer
using five screws. Install the air filter.
Installation
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents